Troubleshooting Guide
Error
Error Type
No.
Inverter compressor over
29
current
I Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
Yes
Is compressor
Wire connection
condition normal?
Yes
Is input voltage normal?
Yes
Is inverter PCB assembly normal?
Yes
Recheck power and installation condition
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Inverter compressor input
current is over 30A
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
No
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
¡ Reassemble or manage if abnormality found
1.Check resistance between each terminal of compressor
(0.188 ±7%)
No
2.Check insulation resistance between compressor terminal
and pipe (over 50MΩ )
¡ Replace compressor if abnormality found
1. Check inverter PCB assembly U,V,W connector
connection condition
No
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
¡ Reassemble if abnormality found
Check
No
L~N phase voltage is 220V ±10%
¡ Check connection condition and wiring if power is
abnorma
No
Check inverter PCB assembly IPM normality
¡ Replace inverter PCB assembly
- 82 -
Main Reasons
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
overcharge)
2. Compressor damage(Insulation
damage/Motor damage)
3. Input voltage low
4. ODU inverter PCB assembly damage
LGE Internal Use Only