A.O. Smith Epsilon EB-40 User Manual page 14

Light commercial high efficiency condensing boiler
Hide thumbs Also See for Epsilon EB-40:
Table of Contents

Advertisement

+
-
Store
Mode
Selection
Type of installation
01
Radiators; air heating; convectors
Radiators with large surface areas or under floor heating as
02
additional heating
03
Under floor heating with radiators as additional heating
04
full under floor heating
= factory setting
When a type of installation has been chosen with a low water-flow temperature it
is possible that in case of a severe winter period the temperature of the heating
system will need to be increased slightly. In such situations the installation choice
may need to be changed, so that a higher flow temperature can be chosen. This
adjustment would normally be carried out by your installer during the installation
and commissioning.
Adjusting the type of installation
The boiler is designed in such a way that it will
adjust itself automatically to what is necessary
for a normal heating system. In some cases the
Step
installation may have convectors or complete un-
derfloor heating.
One can easily choose heating installation adjust-
ments appropriate for the system such as maxi-
Reset
mum water-flow temperature or for the warming up
of the installation after a night period. Adjustment
goes as follows:
-
Press (from the Technical) reading the Mode
key once;
-
Press the Step key twice;
The display will show 2 01.
-
Press the + or the - key to alter the type of
installation according to the table below;
-
Press the Store key to confirm the setting;
The display will flash once.
-
Press the Mode key once;
The display will show StbY for a short while
and will return to the Technical reading.
Flow water
temperature
85°C
70°C
60°C
50°C
14