CHAPTER 4 APPLIED OPERATION
J
Setup
Setting the set point upper limit
Operation Procedure
Initial setting level
Input type
Set point
upper limit
Setting the set point lower limit
Operation Procedure
Set point lower
limit
4-14
To set the set point upper and lower limits, set in the set point upper
limit" and set point lower limit" parameters in the initial setting level".
This example describes how to set the set point limitter  200 to 1300 _ C"
to input type K thermocouple.
200
100
Set the set point upper limit" parameter to 1000".
(1) Press the
key for at least three seconds to move from the opera
tion level" to the initial setting level".
(2) Select set point upper limit".
(3) Press the
or
Set the set point lower limit" parameter to  100".
(1) Select set point lower limit" in the initial setting level".
(2) Press the
or
Sensor range
Set point limitter
key to set the parameter to 1000".
key to set the parameter to  100".
1300
1000