Cutting or extending the pipe
1. Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).
2. If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the
pipe (see below examples of correct and incorrect cut edges).
Pipe
cutter
Pipe
3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.
4. Put a flare nut slightly into the pipe and modify the flare.
Pipe
Flare
5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).
Correct
6. Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench,
applying the following torque:
Indoor outlet pipe
• E xcessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the
pipe (50 Pa). The joint must be accessible and serviceable.
7. For further details on how to connect to the outdoor unit and purge the air, refer to page 37~39.
• T ighten the flare nut with torque wrench according to specified method.
If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.
34
Australia_AQV30T@_IB&IM_33367A_E.indd 34
Oblique
Outer Diameter (D)
Damaged
Inclined
Surface
Flare nut
Connecting pipe
Rough
Burr
Depth (A)
ø6.35 mm
1.3 mm
ø9.52 mm
1.8 mm
ø12.70 mm
2.0 mm
ø15.88 mm
2.2 mm
ø19.05 mm
2.2 mm
ø22.23 mm
2.2 mm
Uneven
Cracked
Thickness
Outer Diameter
Torque (kgf•cm)
ø6.35 mm
ø9.52 mm
ø12.70 mm
ø15.88 mm
ø19.05 mm
ø22.23 mm
Flaring Size (B)
9.0 mm
13.0 mm
16.2 mm
19.3 mm
22.5 mm
25.7 mm
140~170
250~280
380~420
440~480
990~1210
990~1210