Installing And Connecting The Assembly Pipe Of The Indoor Unit - Samsung AQV24 Series Installation Manual

Table of Contents

Advertisement

Connecting the assembly cable
• Also circular terminal must be matched with screw size in terminal block.
• After connecting the cables, make sure terminal numbers on the indoor/outdoor unit matches.
• P lease ensure that Power & Communication cables are separated, they must not be in the same cable.
10. Connect the grounding conductor to the grounding terminals.
11. Close the terminal board cover by tightening the screw carefully.
• I n Russia and Europe, consult with the supply authority to determine the supply system impedance before
installation.
• C onnect the wires firmly so that wires can not be pulled out easily.
(If they are loose, it could cause burn-out of the wires.)
• C onnect the wires according to color codes, referring to the wiring diagram.
• T he power cable and the interconnection cable should be selected according to the specification in page 30.

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless
refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures
of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be
used.
There are 2 refrigerant pipes of different diameters:
• The smaller one is for the liquid refrigerant
• The larger one is for the gas refrigerant
A short pipe is already fitted to the air conditioner. You may
need to extend the pipe using the assembly pipe (optional).
The connection procedure for the refrigerant pipe varies
according to the exit position of the pipe when facing the wall:
• Right(A)
• Left(B)
• Underside(C)
• Rear
1. Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor
unit unless you connect the pipe directly from the rear.
2. Smooth the cut edges.
3. Remove the protection caps of the pipes and connect the assembly pipe
to each pipe. Tighten the nuts first with your hands, and then with a
torque wrench, applying the following torque:
• If you want to shorten or extend the pipes, refer to page33~34.
32
Australia_AQV30T@_IB&IM_33367A_E.indd 32
A
C
Outer Diameter
ø6.35 mm
ø9.52 mm
ø12.70 mm
ø15.88 mm
ø19.05 mm
ø22.23 mm
B
Torque (kgf•cm)
140~170
250~280
380~420
440~480
990~1210
990~1210
2012-6-29 9:20:19