Table 3-5. Typical Hfg2.0 Setup Parameters With Default Values - Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Gas fuel metering valve
Table of Contents

Advertisement

PARAMETER
Part Number
Actuator Type
Command Source
Home
Span
Stop Position
Interpolation Table
Position Loop Constant
Current Loop PID Constants
Proportional
Integral
Derivative
Velocity Loop PID Constants
Proportional
Integral
Derivative
Maximum Velocity
Maximum Force
Maximum Homing Velocity
Maximum Homing Force
Maximum Holding Force

Table 3-5. Typical HFG2.0 Setup Parameters With Default Values

DESCRIPTION
Describes part number of actuator model
Describes type of actuator
Sets type of command signal
Controls the direction the actuator will
move, extending or retracting, to find the
mechanical stop (HOME)
Sets the maximum stroke length,
measured from the HOME position
Sets the signal loss position, measured
from the HOME position
Sets how Demand signal is interpolated
between defined points
Sets the maximum velocity
Sets the maximum force output
Sets the maximum velocity used to find
the HOME position
Sets the maximum force the HFG2.0 will
use to find the HOME position
Sets the maximum force to be used to
hold at the HOME position while the
position demand is < 4.1mA and > 2mA
CH. 3: OPERATING THE HFG2.0
FACTORY
SETTING
Per Drawing
Stand Alone
Analog
Extend
1.0 inches
0.0 inches
Linear
63
2.0
200
0
30
3,000
0
10 in/s
1267 lbf
0.5 in/s
500 lbf
500 lbf
51