Table 3-3. Fault Configuration For Fault Alarm - Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Gas fuel metering valve
Table of Contents

Advertisement

48
Fault Alarm Type
Driver Over Current
Tracking Error
Watchdog Expired
RDC Failure
Retract/Extended
Command
Unregulated Voltage Low
+14 Volts Low
+14 Volts High
-14 Volts Low
-14 Volts High
Input Voltage Low
Input Voltage High
DSP Failure
Electronics Over Temp

Table 3-3. Fault Configuration For FAULT Alarm

Persist Time
Driver current > Max Force equivalent
10 Sec
Driver current > Max Force equivalent
current, Fault. If persists for 1 Min.,
1 Sec
Driver current > 18 Amps, Fault. If
persists for 1 Min., Shutdown
If in RUN state, not in home dead band
10 Sec
and position error > allowable,
If not in overcurrent, RDC not faulted and
feedback not equal to demand, Fault.
If last reset was caused by watchdog
< 1 Sec
timer timeout or illegal address attempt,
< 1 Sec
Tests hardware for RDC failure, sets
N/A
10 Sec
Unregulated voltage low, Fault.
7.5 Sec
< 1 Sec
7.5 Sec
< 1 Sec
7.5 Sec
< 1 Sec
7.5 Sec
< 1 Sec
7.5 Sec
< 1 Sec
Input Voltage > 180 V, Fault.
7.5 Sec
< 1 Sec
N/A
10 Sec
Electronics temp ≥ 110 °C, Fault
HFG2.0 USER GUIDE
Fault Action
current, Fault.
Shutdown
Fault.
Fault.
Fault if RDC failure bit set.
Fault not used.
+14 V supply < 12 V, Fault.
+14 V supply > 16 V, Fault.
-14 V supply > -12 V, Fault.
-14 V supply < -16 V, Fault.
Input Voltage < 75 V, Fault.
Fault not implemented.