S7999D Specifications
Overall approximate size:
9.44"W x 1.84"D x 6.66"H
Speaker, audible alarm (85db)
Operating temperature: -4 to 158°F
Electrical Ratings:
Input voltage: 18-30Vac (24Vac
nominal), 50/60Hz
Input current: 500Ma max
Power consumption: 12w max
Important Changes
The S7999D is backwards compatible (form, fit, and function) to previous S7999B/C
platforms. Due to the power requirement the change from 12Vdc to 24Vac, there are important
wiring changes to note when utilizing the new S7999D, please see product data sheet for
specific information.
The S7999D does not ship with a transformer, a transformer may need to be ordered
separately. Honeywell recommends the AT72D1683 transformer for use with the S7999D
Literature
The following literature contains information on product installation, troubleshooting,
specifications and replacement parts.
Form #66-1200-1: S7999D ControLinks Operator Interface Display Installation Instructions
Form # 65-0321: S7999D ControLinks Operator Interface Display Product Data Sheet
Form# 66-1197-2: S7999D S
Form #65-0315-2: S7999D S
Humidity: 90%, non condensing
Interface connectors: Modbus(2), USB(1)
Enclosure rating: IP 10/NEMA 1
Approvals: FCC Part 15, Class A Digital Device
Component Recognized (for non-continuous
operation): File Number MH17367 (MJAT2, MJAT8).
Operator Interface Display Installation Instructions
ola
Operator Interface Display Product Data Sheet
ola
Underwriter's Laboratories, Inc. (UL) (cUL)