FM200
®
MODEL FG & FD FIRE EXTINGUISHERS
INSTALLATION INSTRUCTIONS
OWNER'S MANUAL
THIS MANUAL IS AN INTEGRAL PART OF THE SYSTEM AND AS SUCH, THE
EXTINGUISHER MUST BE INSTALLED AND MAINTAINED ACCORDINGLY.
U.S. COAST GUARD APPROVED FM APPROVED
No. 162.029/237/0
READ AND COMPLY WITH THESE INSTRUCTIONS, WARNINGS
AND LIMITATIONS BEFORE INSTALLING.
SUITABLE FOR USE FG MODELS: 0°F (-18°C) TO 130°F (54°C)
FD MODELS: 20°F (-7°C) TO 130°F (54°C).
SEA-FIRE MARINE
SEA-FIRE EUROPE LTD
DIVISION OF METALCRAFT, INC
UNIT 7. IO CENTRE. STEPHENSON ROAD
ALWAYS MAINTAIN THIS OWNER'S MANUAL NEARBY
9331 A PHILADEPHIA ROAD
FAREHAM, HAMPSHIRE
FOR OPERATOR REFERENCE.
BALTIMORE, MARYLAND 21237 USA
PO15 5RU, UNITED KINGDOM
TEL 410 687 5500 FAX 410 687 5503
PH: 44 (0) 1329 847225
FX: 44 (0) 1329 847226
OWNERS MANUAL PN: 123-194, REV. B
PRINTED IN USA
Website: www.sea-fire.com
20
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the FM200 FG and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sea-Fire FM200 FG

  • Page 1 AND LIMITATIONS BEFORE INSTALLING. SUITABLE FOR USE FG MODELS: 0°F (-18°C) TO 130°F (54°C) FD MODELS: 20°F (-7°C) TO 130°F (54°C). SEA-FIRE MARINE SEA-FIRE EUROPE LTD DIVISION OF METALCRAFT, INC UNIT 7. IO CENTRE. STEPHENSON ROAD ALWAYS MAINTAIN THIS OWNER’S MANUAL NEARBY...
  • Page 2 Metalcraft/Sea-Fire Marine, Inc., it is the user’s obligation to determine the con- ditions of safe use of this product. The information in this document is offered with no warran- ties or representations as to accuracy or completeness and it is the responsibility of each individual to determine the suitability of the information for their particular purpose(s).
  • Page 3 Dispose of waste and empty cylinders as allowed by current Local, State/Province, or Federal laws and regulations. Section 14 — Transport Information OWNER’S MANUAL & INSTALLATION GUIDE SEA-FIRE FM-200 ® AUTOMATIC FIRE EXTINGUISHER MANUAL: PART NO.123-194 Proper Shipping Name: Heptafluoropropane ID Number: UN3296 Hazard Class: 2.2...
  • Page 4 MSDS No. SF002 MATERIAL SAFETY DATA SHEET Sea-Fire “FG” and “FD” series have passed a rigid testing program and carry a Factory Mutual Research Corp. (FM) and United States Coast Guard (USCG) approval for fire suppression applications in marine pleasure craft, uninspected vessels, and Subchapter “T” inspected vessels, subject to the approval of the local Officer in Charge, Marine Inspection (OCMI).
  • Page 5 24-volt models with 3, 5 or 8 control circuits. Refer to optional equipment section in this manual. REMINDER: Sea-Fire systems shall be considered as supplementary to the number of portable fire extinguishers required on-board and are designed and intended for enclosed...
  • Page 6: Installation

    175x584 DO NOT ATTEMPT TO LOOSEN OR REMOVE ANY EXTINGUISHER COMPONENT. FD500A FD500M 451-500 12.7-14.2 19.5 21.7 6.9x23.0 175x584 DO NOT ATTACH SEA-FIRE EXTINGUISHER ON UNDERSIDE OF COVER OR FD550A FD550M 501-550 14.2-15.6 21.7 23.8 10.8 6.9x27.0 175x680 COMPARTMENT HATCH THAT COULD BE THROWN CLEAR DUE TO POSSIBLE...
  • Page 7 MODEL FD-150 thru FD-1000 APPROVED FOR VERTICAL OR HORIZONTAL MOUNTING cable to avoid kinking. Never form a bend with a radius of less than twelve (12) inches (305mm). Selection of the correct size Sea-Fire cable length will eliminate MODEL FD-1050 thru FD-1500 FOR VERTICAL MOUNTING ONLY cable coil.
  • Page 8 Using care, remove the factory installed actuator lever safely pin from the cylinder. Store safety pin in the nylon retainer provided on the cylinder neck (Figure 6 or 7). d. The Sea-Fire manual/automatic extinguisher is now fully operational.
  • Page 9 THREE (3) YEAR “FG” AND “FD” SERIES LIMITED WARRANTY We warranty to the original retail purchaser, all SEA-FIRE extinguishers for a period of three (3) years after retail purchase against defective material and faulty workmanship. Any system found to be defective during the warranty period will be repaired if possible, or replaced free of charge if classified non-refillable (according to product label) upon the prepaid return of the defective system.
  • Page 10: System Maintenance

    Supplies, which are not included with your Sea-Fire system and should be at hand before indicator light installation, are as follows: 1. Five (5) Ampere in-line fuse and holder 2. Sufficient length of insulated 16 AWG stranded wire. 3. Crimp on wire connectors.