STEP 2:
PREPARE THE VENTING S YSYTEM
STANDARD
FITTINGS
NOTE: If the existing duct is round, you must use a rectangular-to-round
adapter, with a rectangular 3" extension
duct installed between the damper assembly and the adapter to prevent the exhaust damper sticking.
DUCT LENGTH
The total length of the duct system, including straight duct, elbows, transitions, wall or roof caps must not
exceed the equivalent
of 140 feet.
For best performance,
do not use more than three 90 degree elbows.
Below are the standard fittings and their equivalent length in feet.
3 1/4" x 10" to 6" = 5 ft.
>
3 1/4" x 10" roof cap = 24 ft
3 1/4" x 10" 900elbow = 25 ft
3
90°elbow = 10 ft
3 1/4" x 10" wall cap
= 40 ft
45°elbow = 5 ft
Figure 9
3 1/4" x 10" flat elbow
= 10ft
61
To calculate the equivalent length of each duct piece used, see the examples below.
I
Examples
For 3 1/4" x 10" SYSTEMS
For 6" ROUND
SYSTEMS
3-1/4"x10"
14----- 6ft. --_1
_[3wall cap
90° elbow _\
H,
2ft.
1-3 1/4" X 10" 90 ° elbow
=
1-Wall
Cap
=
8 feet straight
duct
=
TOTAL
LENGTH
=
25 ft.
40 ft.
8ft.
73 ft.
90° elbows
_----
6ft. --_[_/wall
cap
transi_
1-transition
=
5 ft.
2-90 ° elbows
=
20 ft.
1-Wall
Cap
=
40 ft.
8 feet straight
=
8 ft.
TOTAL
LENGTH
=
73 ft.