Page 2
PowerStar Data Sheet : GLUPS (GLOBAL UPS) 1500 va UPS GLUPS PS-1501VI Global Universal Deployable UPS PowerStar Inc. 9073 Shady Grove Ct. Gaithersburg, Md. 20877 250/110v 47-63hz hz input 110 -120 v 50/60 hz output or 120-110v 50/60hz SOLVES OVERSEAS POWER AND PRINTER REQUIREMENTS...
Page 3
PowerStar Inc. Mission Critical Power 9073 Shady Grove Gaithersburg Maryland 20877 800-209-5556 301-948-0713 http://www.powerstarinc.com/power.html...
Page 4
1. Cooling and Fan Operation of -UPS INFORMATION: All PS-1501vi -UPS , have cooling fans. Fan cooling runs during four normal, though in most cases infrequent, modes of operation. These modes are listed as follows: 1 ) The fan is on whenever the UPS is operating on-battery. 2 ) The fan is on when the UPS' internal ambient temperature exceeds 60!C (140!F).
Page 5
1.6 at full load and 2 at 1/2 load. This is much better performance than a typical power conditioner or UPS. PowerStar UPS systems are designed to maintain the proper peak voltage into the computer load for computers with any input crest factor specification.
Page 6
1.5 times the steady-state power consumption. All PowerStar UPS systems have enough surge factor capability to start typical hard disk loads even when the UPS is operated at the full power rating.
APC's knowledge base http://www.apcc.com, for the particular problem, or contact APC technical support at 800-800-4272. Or contact PowerStar Inc. at http://www.powerstarinc.com 5. Cooling and Fan Operation of -UPS TOPIC Operation of -UPS' internal cooling fans, temperature thresholds and conditions for forced ventilation...
Page 8
INFORMATION All -UPS 1400, 2200, 3000, and XL models have cooling fans. Fan cooling runs during four normal, though in most cases infrequent, modes of operation. These modes are listed as follows: 1 ) The fan is on whenever the UPS is operating on-battery. 2 ) The fan is on when the UPS' internal ambient temperature exceeds 60!C (140!F).
Page 9
- 208 Volt Applications For 208 volt applications, any two of the hot phase conductors will be connected to the X and Y terminals of a suitable NEMA X6-XX receptacle. The ground wire will be connected to the ground lug (colored green). 7.
Page 10
Important: The top connectors ar OCONUS and the bottom connectors are CONUS and output. This unit will only output 110-132v 50/60 hz. Any attempt to use other voltages will damage equipment and VOID the warranty. Organization This document is organized by situation. The potential hazards corresponding with the situation are identified.
Page 11
Please refer to the UPS instructions for the power cord and output selections available to you. Technical support is always available at Powerstar. In the US call 800-209-5556. International calls can be made to 301-948-0713. Fax to 301-948-2094. Email to : jcarr@powerstarinc.com...
Page 12
OCONUS COUNTRY CORDS DATA SHEET ps1501vi FOR TRANSFORMER # 6575 POWERSTAR INC.002-1011 page 1 of 1 ------------------------------------------------------------------------------------------------- LEADS SCHEMATIC LEADS S#14/10" BLUE WHITE S#12/10" UO = 125.9V RMS S#14/10" 240V BROWN BLACK 120V RMS / 1500VA S#12/10" PRIMARIES ARE INSIDE A SLEEVE.
Page 13
11. Power, Crest, And Surge Factors Introduction This Technical Note explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms in specifying UPS is explained. Power factor Power factor is a quantity which has important implications when sizing a UPS system.
Page 14
1.6 at full load and 2 at 1/2 load. This is much better performance than a typical power conditioner or UPS. PowerStar UPS systems are designed to maintain the proper peak voltage into the computer load for computers with any input crest factor specification.
Page 15
Manual to change this value. When this amount of time runs down, the UPS/Power Array goes to sleep. 12. Maintenance And Troubleshooting the UPS Addendum 2001--For qualified Technicians only-Confidential to US government and Powerstar Inc. 1.1 UPS Modification of parameters: Flexability Builtin...
Page 16
The Ps1501vi, Ps700vi, PS6000, PS6002, and PS6003 and strainless steel version UPS are microprocessor controlled and is capable of RS-232 communications through a computer interface port at its rear panel. When combined with power management software and a serial communications interface cable, the PS6000 ups allows flexibility in controlling UPS operation via computer.
Page 17
UPS, and do individual battery tests. Battery warranty from our OEM supplier is two years. If a technician is in a remote location APC, can swap batteries by knowing the serial number on the back. Battery swaps are at 18008004apc. Also, tech support is always available at that number. Powerstar , not APC, can support our modifications, such as the mil connectors. Powerstar tech support is always available too.
Page 18
C. Service of the isolation transformer is only needed when the UPS is dropped, a military attack which dislodges the unit from its brackets, or a wire is severed. D. To remove, all power must be removed from Ups. We recommend that you contact powerstar first, and we will assist you free of charge. But if needed, it has two primary hot wires, and two secondary neutral wires.
Page 19
2001 Powerstar Inc . All rights reserved This document is confidential and is covered by the copywrite law s of the USA Powerstar Inc. Gaithersburg Maryland 301-948-0713 http://www.powerstarinc.com Price of this manual is $39.00...
Need help?
Do you have a question about the GLUPS PS-1501VI and is the answer not in the manual?