CMY-Y100CBK3
For Gas pipe:
19-29/32"
Pipe cover
(Dot-dashed part)
Local brazing
1-1/8"
1-1/8"
Note 2
13-15/32"
Distributer
23-5/32"
ID: Inner Diameter
OD: Outer Diameter
Note 1. Reference the attitude angle of the branch pipe below the fig.
The angle of the branch pipe for high pressure is within
2. Use the attached pipe to braze the port-opening of the distributer.
3. Pipe diameter is indicated by inside diameter.
4. Only use the Twinning pipe by Mitsubishi (optional parts) .
Notes:
Mitsubishi Electric Air Conditioning & Refrigeration Systems Wo rks acquired ISO
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.
ISO Authorization System
The ISO 9000 series is a plant authorization system relating to quality warranties as
development, production, installation and auxiliary services" for products built at
an authorized plant.
Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO).
CMY-Y100CBK3
Twinning Kit:
For Liquid pipe:
1"
7/8"
5/8"
7/8"
5/8"
1"
Distributer
7-7/32"
1/2"
1/2"
Local brazing
1/2"
Note 2
Pipe cover
3-9/32"
1/2"
(Dot-dashed part)
Distributer
9-1/2"
15
against the horizontal plane.
Specifications are subject to change without notice.
Ref.: CMY_Y100VBK2_EXD_EUDB_SI
<Reducer(Accessory)>
5/8"
1/2"
3/8"
1-15/16"
1-15/16"
(2 pcs.)
1-1/8"
7/8"
7/8"
2-15/32"
2-15/32"
(2 pcs.)
(2 pcs.)
Mitsubishi Electric Sales Canada Inc.
www.MitsubishiElectric.ca
SB_PUHY-P192TSKMU-A_201206
in.
1/2"
3/4"