Setting The Btc Controller - Grant Aerona HPAW110 Installation And User Instructions Manual

Grant aerona air source heat pump
Hide thumbs Also See for Aerona HPAW110:
Table of Contents

Advertisement

11 Commissioning
Figure 11-2: BTC display and buttons
32

11.3 Setting the BTC Controller

To set the BTC controller.
1. Press all 3 buttons for 1 second to
enter the mode setting.
2. If 'Mode1' is shown, press the
button until 'Mode 3' is displayed
then press 'Item again. 'OUTDR
START' should now be displayed.
3. Scroll through the menu using the
button, the 'Item' button to
access the desired function. Use
the
or
button to alter the
setting.
4. Press the 'Item' button once more
to go back to the menu.
The BTC incorporates 2 digital
temperature controls – one for the CH
and one for the DHW.
The purpose is to give far greater
control over the heating system than
conventional controls allow.
If UFH (Under Floor Heating) and
Radiators are on the same system you
may want the system to work around a
flow temperature of 50˚C. If UFH alone,
then the flow temperature could be a
35˚C flow. When a DHW demand is
present, you may want to use the heat
pump to take the water to 60˚C, or
alternatively you may wish to preserve
the COP and therefore the efficiency
and only raise the cylinder to 50˚C.
This control allows you to be in control.
When operating in DHW mode, the
ambient air temperature is ignored.
However, in CH mode (without DHW
demand) the ambient outside
temperature is used to determine how
much input power is required to
achieve the desired target temperature.
This provides a very efficient way to
weather compensate the heating
system which will add to the heat pump
and the system efficiency.
!
NOTE
This increase in efficiency has NOT
been taken into account in the COP's
quoted on the technical
specifications table.