Existing Fireplace Installation - Harman Stove Company P35i Owner's Manual

Pellet/biomass fireplace insert #1-70-774195 #1-70-774235
Table of Contents

Advertisement

P35i Fireplace Insert
D. Existing Fireplace Installation:
If using a short run of venting, whether flex or rigid,
through the damper and into the chimney flue; The
Damper must be removed or locked in the open posi-
tion and sealed with a plate constructed of steel or
other non-combustible material.
Kaowool, mineral wool or other non-combustible insu-
lation is recommended above the plate to reduce the
possibility of condensation. You will also need to wrap
the venting section between the insert frame and the
damper sealing plate. This is to prevent overheating
of the fireplace cavity, which may cause damage to
the insert's motors and other electrical components.
The connector pipe should extend through the sealing
plate and smoke chamber and into, or beyond the first
flue tile.
IN CANADA: This fireplace insert
must be installed with a continuous
chimney liner of a minimum 3"
diameter extending from the insert to
the top of the chimney. The chimney
liner must conform to the Class 3
requirements of CAN/ULC-S635,
Standard for Lining Systems for
Existing Masonry or Factory Built
Chimneys and Vents, or CAN/ULC-
S640, Standard for Lining Systems
for New Masonry Chimneys.
Non-combustible
Insulation
Save These Instructions
When venting in this configuration, a rain cap and
proper flashing must be installed on the top of the
chimney to prevent flooding and damage.
Sealing Plate
Be sure to design the venting so that it can be easily
cleaned.
Check with your local authority having jurisdiction to
determine if this venting method is acceptable. Some
Provincial, State, or Local codes may require a full
liner run to the top of the chimney. Be sure and check
your local regulations before planning the installation.
In this method, the proper flashing and rain cap are
also required.
Fire Risk.
Inspect Chimney
Masonry chimney must be in good condition
Meets minimum of NFPA 211 standard
Factory-built chimney must meet requirements
of UL103 HT
3-90-775
WARNING
When using single wall flex, this
section of venting must be
wrapped with non-combustible
insulation to prevent excessive
heat build-up in the cavity.
Pellets or Corn/Pellet Mixture Only
15