Troubleshooting - York LX series Owner's Manual

Residential digital thermostat backlit display
Hide thumbs Also See for LX series:
Table of Contents

Advertisement

TroubleShooting

SYMPTOM: The air conditioning does not attempt to turn on.
YOUR NAME
I
2:00
Am
MO
74
OO
C
L S
ET
78
Outdoor
H
S
85
EAT ET
68
CAUSE: The compressor timer lockout may prevent the air
COOLER
MODE
WARMER
conditioner from turning on for a period of time.
REMEDY: Consult the Owner's Manual in the Installer Setup
section to defeat the Cycles Per Hour (page 22).
SYMPTOM: The display is blank.
YOUR NAME
I
Am
MO
2:00
74
OO
C
L S
ET
78
H
S
Outdoor
EAT ET
CAUSE: Lack of proper power.
85
68
COOLER
MODE
WARMER
REMEDY: Make sure the power is on to the furnace and that
you have 24vac between R & C.
SYMPTOM: The air conditioning does not attempt to turn on.
YOUR NAME
I
2:00
Am
74
MO
C
L S
OO
ET
78
Outdoor
H
EAT ET
S
CAUSE: The cooling setpoint is set too high.
85
68
COOLER
MODE
WARMER
REMEDY: Lower the cooling setpoint or lower the cooling set-
point limit. See Setpoint Limits (page 22).
SYMPTOM: The heating does not attempt to turn on.
YOUR NAME
I
2:00
Am
74
MO
C
L S
OO
ET
78
Outdoor
H
EAT ET
S
CAUSE: The heating setpoint is set too low.
85
68
COOLER
MODE
WARMER
REMEDY: Raise the heating setpoint or raise the heating set-
point limit. See Setpoint Limits (page 22).
SYMPTOM: When controlling a residential heat pump, and
YOUR NAME
I
2:00
Am
MO
74
OO
C
L S
ET
78
Outdoor
H
EAT ET
S
85
68
asking for cooling, the heat comes on.
COOLER
MODE
WARMER
CAUSE: The thermostat reversing valve jumper is set for "B".
REMEDY: Set the reversing valve jumper for "O".
SYMPTOM: When calling for cooling, both the heat and cool
YOUR NAME
I
2:00
Am
74
MO
C
L S
OO
ET
78
Outdoor
EAT ET
H
S
85
68
come on.
COOLER
MODE
WARMER
CAUSE: The thermostat equipment jumper is configured for
"HP" and the HVAC unit is a Gas/Electric.
REMEDY: Set the equipment jumper for "Gas".
SYMPTOM: When the Program button is pressed, the display
YOUR NAME
I
2:00
Am
74
MO
C
L S
OO
ET
78
Outdoor
EAT ET
H
S
85
68
reads "DISABLED".
COOLER
MODE
WARMER
CAUSE: Program mode is set to "NON PROGRAM".
REMEDY: Set Program Mode (Setup 1) to 1, 5/2, or 7 Day.
See Selecting Your Program Mode (page 21).
Page 37