Timers And Deadbands - York LX series Owner's Manual

Residential digital thermostat backlit display
Hide thumbs Also See for LX series:
Table of Contents

Advertisement

Installer Setup
Deadband Settings (Setup Steps 25 - 34)
The Deadband is the number of degrees or minutes that the thermostat
waits before it initiates the stages of heating or cooling.
1st Stage Deadband (Setup Step 25) - Specifies the minimum temperature difference
between the room temperature and the desired setpoint before the first stage of heating
or cooling is allowed to turn on. (1 - 6 degrees) For example, if the heat setpoint is 68
and the 1st Stage deadband is set to 2 degrees, the room temperature will need to
reach 66 degrees before the heat turns on.
2nd Stage Deadband (Setup Step 26) - Specifies the additional minimum temperature
difference after the first stage turns on before the second stage is activated. (0 - 10 )
3rd Stage Deadband (Setup Step 27) - Specifies the additional minimum temperature
difference after the second stage turns on before the third stage is activated. (0 - 10 )
4th Stage Deadband (Setup Step 28) - (Two Stage heat pump only) - Specifies the
additional minimum temperature difference after the third stage turns on before the
final stage of strip heat is activated. (0 - 10 )
Minutes Between 1st and 2nd Stage (Setup Step 29) - Specifies the minimum time
(in minutes) after the first stage turns on before the second stage can turn on. (0 - 60)
Minutes Between 2nd and 3rd Stage (Setup Step 30) - Specifies the minimum time
(in minutes) after the second stage turns on before the third stage can turn on. (0 - 60)
Delay Between 3rd and 4th Stage (Setup Step 31) - Specifies the minimum time
(in minutes) after the third stage turns on before the final stage can turn on. (0 - 60)
Second Stage on Until Deadband (Setup Step 32) - Specifies whether second stage
will turn off at first stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Third Stage on Until Deadband (Setup Step 33) - Specifies whether third stage will
turn off at second stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Fourth Stage on Until Deadband (Setup Step 34) - Specifies whether fourth stage
will turn off at third stage deadband or remain on until the room temperature demand is
satisfied. Choose between Deadband or Setpoint.
Page 23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S1-tbsu32p7yS1-thsu21p1S1-thsu32p7S1-thsu32hp7

Table of Contents