Cold Weather Kit; Reconfiguring The Fuel System - Generac Power Systems 1.6L 18 kW Owner's Manual

1.6l 18 kw models standby generator sets
Table of Contents

Advertisement

GENERATOR
CONNECTION
BOX
120 Volt +
Neutral
Grd
Ground Level
Concrete Slab

COLD WEATHER KIT

For cold climates, optional cold weather kit (part
number 0F6148) is recommended. The kit includes:
• Battery Warmer
• 4" Junction Box with hardware
• 6 qt. pack 5W-30 synthetic oil (engine)

RECONFIGURING THE FUEL SYSTEM

All models are configured to run on natural gas
from the factory.
To reconfigure the fuel system from NG to LP , follow
these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet
port of the demand regulator (see Figure 6.2).
3. Disconnect the power wires from the fuel sole-
noid located on top of the regulator assembly.
4. Loosen the spring clamp on the small fuel enrich-
ment line and remove the hose from the hose
barb.
5. Remove the black pipe assembly from the outlet
port of the demand regulator.
6. Remove the NG fuel jet (loosen counter clock-
wise) from the outlet port.
7. Remove the LP fuel jet (loosen counter clockwise)
from the jet keeper port on the side of the regula-
tor housing. Install this jet into the outlet port in
the regulator casting.
04/07
A
Rev.
GenSpec038
Standby Generator Sets
Figure 6.1 — Interconnections
CONTROL PANEL
TO
ALTERNATOR
N1
NEUTRAL
N2
23
194
CIRCUIT
BREAKER
183
178
Battery
Charger
Input
GROUND
FRAME RAIL
STUB-UP AREA
See Install Dwg for
Dimensions
NOTE:
Specifications
Transfer Switch
4- # 14 GA
WIRES TO
GENERATOR
CONNECTION
BOX
The jet sizes are stamped on the individual jets.
The larger jet size is used for running on NG.
8. Install the previously removed NG jet into the jet
keeper port on the side of the regulator housing.
9. Install the previously removed black pipe onto
the outlet port of the demand regulator.
10. Reverse steps 1-4 in this procedure to reactivate
the demand regulator.
Figure 6.2 — Reconfigure the Fuel System
Serious injury or damage may occur if not con-
figured properly. Please consult an Authorized
Dealer with any questions.
6-2
Utility In
NEUTRAL
Gen
N1
N2
23
194
Load
186
Out
178
TO GENERATOR
CONNECTION BOX
To Generator Control Panel
CIRCUIT BREAKER SIZE
KW
VOLTS
/
AMPS
LUG SIZE
25
240 1 Ø
125
#4 to 1/0
25
208 3 Ø
100
#4 to 1/0
NOTE: