Appendix A
PowerchiefR Series
Information in this Appendix applies to the following Baldor Generators:
PC30H, PC40H, PC50H, PC60H, PC90VE
Caution:
The brass connecting tab on some 120VAC duplex receptacles have been removed. Each
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect
the brass tab that normally links both receptacles. If it is removed, be sure to remove the
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will
cause a direct short to the generator windings and cause possible generator damage.

Operator Panel Configuration

Press to Reset
Press to Reset
MN2412
Figure A-1 PC30H Operator Panel
Figure A-2 PC40H, PC50H, PC60H, PC90VE Operator Panel
PowerchiefR Series A-1