GE Powervent AP13787 Use And Care Manual page 13

Gas residential 40 and 50 gallon
Table of Contents

Advertisement

Maximum and Minimum Vent Lengths
NOTICE: The mixing of 2" and 3"
vent pipe is not recommended. If
3" pipe is used, a 2" to 3" bell
coupling is recommended at the
rubber coupling.
This water heater is supplied with
a two-inch Schedule 40 PVC 45°
vent terminal. If you decide to vent
with 3" pipe, a Schedule 40 DWV
PVC 45° vent terminal must be
used. For your convenience
screens for both 2" and 3" vent
terminals have been included.
Minimum vent length for 2" vent pipe is one (1) foot of vertical pipe, one (1)
90°elbow, and three (3) feet of horizontal pipe.
Venting information for 2" Vents*
Number of 90° elbows
with Vent
One (1)
One (1)
Two (2)
Two (2)
Three (3)
* For the 2" vent, one 90° elbow is approximately equal to 6 feet of pipe. One
45° elbow is approximately equal to 3 feet of pipe.
Minimum vent length for 3" vent pipe is one (1) foot of vertical pipe, one (1)
90°elbow, and four (4) feet of horizontal pipe.
Venting information for 3" Vents**
Number of 90° elbows
with Vent
One (1)
One (1)
Two (2)
Two (2)
Three (3)
Three (3)
Four (4)
Four (4)
Five (5)
** For the 3" vent, one 90° elbow is approximately equal to 5 feet of pipe.
One 45° elbow is approximately equal to 2.5 feet of pipe.
Number of
Maximum Pipe Length
45° Elbows
None
One (1)
None
One (1)
None
Number of
Maximum Pipe Length
45° Elbows
None
One (1)
None
One (1)
None
One (1)
None
One (1)
None
in Feet (ft)
44.00
41.00
38.00
25.00
32.00
in Feet (ft)
95.00
92.50
90.00
87.50
85.00
82.50
80.00
77.50
75.00
13