Quick setup
8.
Quick setup
Following these instructions, you can easily and fast set up your BACnet bus for use:
Choose control place.
1
A. Press LOC/REM button on keypad to select
B. Select
Ctrl. Place (P1.15) > FieldbusCTRL
Make these settings in the master software
A. Set
Control Word
B. Set
Control Word
C. Frequency converter status is RUN
2
D. Set Reference value to '50' (50.00%) (AV24 Speed Reference).
E.
Frequency setpoint
F. Set
Control Word
G. Frequency converter status is STOP.
as remote control place:
Fieldbus
to '0' (AV36 Fb_Control_Word_Lo16)
to '1' (AV36 Fb_Control_Word_Lo16)
is 25.00 Hz (if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
to '0' (AV36 Fb_Control_Word_Lo16)
Remote Control Place
>
Main Menu
Quick Setup (M1)
Honeywell • 36
>
Rem.