Honeywell • 13
4.2

Prepare for use through MS/TP

Strip about 15 mm of the RS485 cable (see specification on page 8) and cut off
the grey cable shield. Remember to do this for both bus cables.
Leave no more than 10 mm of the cable outside the terminal block and strip the
cables at about 5 mm to fit in the terminals. See picture below.
3
Also strip the cable now at such a distance from the terminal that you can fix it to
the frame with the grounding clamp. Strip the cable at a maximum length of 15
mm. Do not strip the aluminum cable shield!
Then connect the cable to its appropriate terminals on Honeywell SmartDrive
4
standard terminal block, terminals A and B (A = negative, B = positive). See
Figure 7.
21 22 23
13 14 15 16 17 18 19 20 A
12
2 3 4 5 6 7 8 9 10
1
RS485
terminals
(A and B)
2829
24 25 26
B
11
Figure 7.
BACnet installation
10
5
B
20
A
8 9 10
11