Honeywell BacNet protocol Installation And User Manual page 19

For variable frequency drives
Table of Contents

Advertisement

Honeywell • 17
Code
Parameter
MONITORING VALUES
Fieldbus protocol
P5.7.3.2.1
status
Communication sta-
P5.7.3.2.2
tus
Actual instance
P5.7.3.2.3
number
P5.7.3.2.4
Fault code
P5.7.3.2.5
Control word
P5.7.3.2.6
Status word
Table 5. Parameters related with BACnet used through MS/TP
Min
Max
Unit
1
3
0.0
99.999
0
65535
0
3
hex
hex
Default
ID
1 = Stopped
2 = Operational
3 = Faulted
0-99 Number of mes-
sages with errors
0.0
0-999 Number of mes-
sages without communi-
cation errors
Shows actual Device
Serial
Object's instance num-
number
ber
0 = None
1 = Sole Master
0
2 = Duplicate MAC ID
3 = Baud rate fault
See chapters 6.2 and
6.3.
See chapters 6.2 and
6.3.
Programming
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents