GE Digital Energy LP 33 Series Operating Manual page 36

50 & 60 kva
Hide thumbs Also See for Digital Energy LP 33 Series:
Table of Contents

Advertisement

3.
Switch On the output switch Q1 (Pos. I).
The output will be supplied by the mains through the bypass.
Verify, selecting the screen METERING/Udcp and Udcn, that the
booster voltage has reached about 215 VDC.
4.
Switch On the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON
Some seconds later the load will be transferred on inverter
and the main screen will display: APPLICATION ON UPS
5.
Operation mode selection.
LP 33 Series is delivered normally selected for permanent VFI operation.
ECO Mode can be enabled and the ECO START time & ECO STOP time can be programmed for each
day of the week (see Section 6.3.1-5).
NOTE !
Even if the UPS is delivered with fully charged batteries, they could be partially
discharged during transportation or storage.
It is recommended to recharge batteries for few hours in order to provide complete
battery energy stored to the load in the event of mains failure.
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
END OF PROCEDURE
LP 33
60kVA
APPLICAT. ON UTILITY
= xx%
Udcp=215V
Udcn=215V
Ubp=164V
Ubn=164V F
Charge level
= 100%
Autonomy
= xxxmin
COMMAND MENU
INVERTER ON
INVERTER OFF
LP 33
60kVA
APPLICATION ON UPS
= xx%
Operating Manual LP 33 Series 50 & 60 kVA
*
Page 36/57