GE Digital Energy LP 33 Series Operating Manual page 24

50 & 60 kva
Hide thumbs Also See for Digital Energy LP 33 Series:
Table of Contents

Advertisement

Code
Alarm
BATTERY
4118
FAULT
TURN ON RECT.
4130
OR SHUTDOWN UPS
RECTIFIER
4140
CONTROL FAILURE
INVERTER
4301
FUSES FAILURE
K7 CLOSING
4304
FAILURE
K7 OPENING
4305
FAILURE
INV. VOLTAGE
4312
OUT OF TOLERANCE
ISMAX
4320
DETECTION
INVERTER
4340
CONTROL FAILURE
OSCILLATOR
4347
FAILURE
RECTIFIER
4402
CANNOT BE TURNED ON
K6 CLOSING
4404
FAILURE
K6 OPENING
4405
FAILURE
BYPASS MAINS
4410
OUT OF TOLERANCE
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
During battery test the DC voltage falls under the critical
level.
If the boost voltage has not been reached within 24 hours,
then the charge voltage returns to floating voltage.
Battery test is stopped.
Rectifier and inverter are OFF.
The DC power supply is discharging the battery slowly.
Rectifier must be restarted or battery must be disconnected
in order to avoid damages.
Rectifier voltage hasn't reached the set value.
Probably fault on regulation loop.
The DC capacitors are not equally charged (more of 50 VDC
of difference).
The rectifier is switched OFF.
Inverter output fuses blown.
Signaled by electronic detector.
Inverter can be started manually after replacement of fuses.
K7 not closed despite a closing command being done.
Signaled by auxiliary contact.
Load will be supplied by mains.
K7 not open despite an opening command being done.
Signaled by auxiliary contact.
Load will be supplied by mains.
Inverter output voltage is out of the tolerances defined in
respective parameter (±10%).
Inverter is switched OFF.
Detection of inverter bridge (Is) current limitation cause
inverter OFF and automatic restart (message 320).
After 3 times inverter switches OFF for persistent Is max
detection in time.
Inverter switch OFF, and it can be restarted manually.
The slave oscillator is not synchronized with the master, thus
causing the shutdown of it's inverter.
Auto calibration of the Inverters free-run frequency was not
possible.
The oscillator frequency of this unit is out of tolerance.
The rectifier cannot be turned on because the DC link
voltage has not reached the requested value.
K6 not closed despite a closing command being done.
Signaled by auxiliary contact.
The load cannot be supplied by electronic bypass.
K6 not open despite an opening command being done.
Signaled by auxiliary contact.
The mains bypass voltage is out of the tolerances (±10%).
K6 opens, synchronization with mains is inhibited and
transfer to mains is blocked.
Meaning
Operating Manual LP 33 Series 50 & 60 kVA
Page 24/57