SPECIFICATIONS
MODEL NO. ........... MH35LP
GAS TYPE ................. LP-Gas
MAX. INLET
PRESSURE. .......... 27.5" W.C.
MIN. INLET
PRESSURE ........... 27.5" W.C.
MANIFOLD
PRESSURE ........... 25.5" W.C
Do not exceed the gas supply pressures shown on rating plate
for Model MH35LP. The maximum inlet gas supply pressure and
the minimum inlet gas supply pressure (for purposes of input
adjustment) for LP-Gas are shown as follows:
WARNING
DO NOT EXCEED 27.5" W.C. (1 psi) INLET
PRESSURE TO HEATER.
CLEARANCE (Minimum clearances to combustible materials)
MODEL NO.
BTU/HR RATING
TYPE GAS
NATURAL
MH35LP
*Tank size and tank temperature can directly affect BTU output
CONTENTS
Installation Instructions ..................................................... 3
Location ............................................................................ 3
Piping ............................................................................... 3
Operating Instructions ...................................................... 4
Lighting and Shut Down ................................................... 4
Maintenance Instructions .................................................. 5
Replacement Parts List ...................................................... 6
Service and Parts Ordering Information ............................. 8
Enerco Group, Inc. | Gas-Fired Infra-Red Portable Construction Heater
NORMAL OPERATING
POSTION
LP & NG
35,000*
VERTICAL
VENTILATION
WARNING
THIS APPLIANCE IS UNVENTED AND MUST BE
USED ONLY IN A WELL VENTILATED AREA.
The ow of combustion and ventilation air must not be
obstructed. DO NOT use in a tightly enclosed area. Any
combustion process requires and consumes oxygen, and may
produce carbon monoxide. This heater must be operated with
adequate ventilation. Two openings directly to the outdoors must
be provided, one low and one high, preferably on opposite sides
of the area to be heated. Each of these openings must provide
at least three square inches of combustion air-intake area and
exhaust outlet area for every 1000 BTUs per hour of heater input
rate in order to complete the combustion/ventilation process.
Provide additional ventilation for any additional fuel-burning
appliances and/or additional occupants.
TOP
40"
FOR YOUR SAFETY
Do not use this heater in a space where
gasoline or other liquids having flammable
vapors are stored or used.
The heater is designed and approved for use as a construction
heater under ANSI Z83.7 / CGA 2.14 - 2000
We cannot anticipate every use which may be made of our
heaters. CHECK WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF
YOU HAVE QUESTIONS ABOUT APPLICATIONS.
Other standards govern the use of fuel gases and heat producing
products in specific applications. Your local authority can advise
you about these.
This appliance is intended to be used primarily for the heating of
buildings under construction, alteration or repair.
THE STATE OF CALIFORNIA REQUIRES THE FOLLOWING WARNING:
WARNING
Combustion by-products produced when using this product contain
carbon monoxide, a chemical known to the State of California to
cause cancer and birth defects (or other reproductive harm).
2
Operating Instructions and Owner's Manual
CLEARANCES TO
COMBUSTIBLES
SIDES
BACK
FRONT
40"
0"
54"