5.3.2 LOCKOUT

If the fault is persistent or more severe the boiler will lockout with a error code. When the boiler
has entered this error mode it will not attempt to restart until the "Reset" button is pressed.

ERROR CODES

Display
Description of fault
E 00
Flame detected when not expected. Check boiler earth and probe condition.
E 02
No ignition after restart. Check gas supply, gas valve operation and ignitor
electrode spark generation
E 03
Gas valve faulty or not connected
E 04
Power has been reset whilst boiler was in lockout
E 11
Internal electronics error - rest or replace control box
E 12
Thermal fuse blown or flue overheat thermostat activated.
E 18
Flow overheat - check water circulation
E 19
Maximum return temperature exceeded. Check circulation.
E 25
Flow temperature increased too quickly. Check water circulation.
E 28
Fan not rotating - check fan connection and fan for fault.
E 30
Difference between flow and return temperatures too high. Check circulation.
E 31
Flow thermistor short circuit - check/replace connections/thermistor
E 32
Return thermistor short circuit - check/replace connections/thermistor
E 36
Flow thermistor open circuit - check/replace connections/thermistor
E 37
Return thermistor open circuit - check/replace connections/thermistor
E 44
Low water pressure
Installation & Servicing Instructions
Chapter 5 : Fault Finding
The Keston C40, C40P, C55 & C55P
Page : 27