Honeywell VisionPRO IAQ Installation Manual page 4

Touch-screen programmable thermostat
Hide thumbs Also See for VisionPRO IAQ:
Table of Contents

Advertisement

Available languages

Available languages

Installation Guide
Installer setup
Setup function
0370
Indoor humidity
sensor
0372
Indoor humidifica-
tion control
0374
Humidifier fan action
0379
Dehumidification
control
0383
Over-cooling limit
0384
Dehumidification
fan action
0386
Whole house
dehumidification
lockout
0390
Dehumidification
away mode
0391
Dehum. away mode
fan setting
0392
Dehum. away mode
low limit temp.
0393
Dehum. away mode
temp. setting
0394
Away dehumidifica-
tion setting
0400
Ventilation control
0401
Number of
bedrooms
0402
Size of house
0403
Ventilation level
0404
Max. ventilation
% limit
* DATS required for Desert Humidification.
69-1816EFS—09
Settings & options (factory default in bold)
1
Internal sensor in thermostat
0
Sensors disabled
E
Auto Discover
**
E
Auto Discover
**
0
Off
1
Humidify (no frost protection)
3
Humidify (with frost protection)
8
Desert Humidity Control in heat, cool, and off (no frost
9
Desert Humidity Control in heat, cool, and off (with frost protec-
tion)*
0
Humidify only while fan or heat is on
1
Humidify forces fan on
2
Humidify only when heat is on
3
Humidifier operates independent of fan
0
No dehumidification control
1
Dehumidify with air conditioner
3
Whole house dehumidifier
3
3°F (1.5°C)
[Other options: 1, 2 (1°F or 2°F/0.5°C to 1.5°C)]
0
System fan turns on with dehumidifier
1
Dehumidifier operates independent of fan
0
Disabled
1
Enabled
0
No
1
Yes
0
Fan auto
1
Fan always on
2
Fan circulate
76
Low limit temperature 76°F (24°C)
[Other options: 70°F to 80°F (21°C to 27°C)]
85
Away temperature 85°F (29°C)
[Other options: 70°F to 99°F (21°C to 37°C)]
65
Away humidity level 65%
[Other options: 40% to 70%]
0
No ventilation
1
Ventilation always allowed
2
Ventilation not allowed during sleep period
3
Vent all with lockouts
4
Vent off sleep with lockouts
2
Two bedrooms
[Other options: 1 to 6]
10
1,000 square feet
[Other options: 11 to 50 (1,100 to 5,000 square feet)]
160 CFM (cubic feet per minute)
[Other options: (30 to 195 CFM)]
50
50% ventilation limit
[Other options: 30% to 60% or 100%]
P
Meets ASHRAE 62.2 standard
F
Does not meet ASHRAE 62.2 standard
4
protection)*
**See pages 6 & 7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents