14
en | Connection
Terminal
FPE-1000-NW
Table 5.2 Specifications SLC Terminals Class A Style 7
Additional notes regarding Class A Style 7:
1.
2.
3.
4.
Figure 5.1 Network Connections Example
Legend
1
2
3
4
5
NOTICE!
The network does not require an EOL resistor.
F.01U.214.374 | 01 | 2012.08
Wired OUT+/-
Wired IN+/-
No T-taps allowed on Class A Style 7 network wiring.
The return side of the loop must be routed separately from the outgoing loop.
The return side must not share the same conduit or cable as the outgoing side of the
loop.
Refer to NFPA 72 for additional requirements of Class A circuits.
Wire to Wire connection
Wire to Ethernet connection
Ethernet to Fiber Optic connection
Fiber Optic to Fiber Optic connection
Class A connection (Ethernet to Ethernet in this example)
Installation Manual
Specifications Class A Style 7
Terminals used for outgoing loop
Terminals used for return loop
Bosch Security System, Inc.
Networking Cards

Advertisement

Table of Contents