2.3
Wiring
Make sure all power is removed before
making any electrical connections. Failure
to do so may result in personal injury and/or
damage to equipment.
Run all wires and make all connections before
mounting the FMM-7045/FMM-7045-D. All wiring is
supervised and power limited. See Figure 2 for details.
Do not loop wire around each terminal.
Break terminal wire connections for
supervision.
Figure 2:
Wiring the FMM-7045
2
1
3
L
o
o
p
+
0
9
8
7
6
5
TENS
1 - Previous device or D7039/DS9431
2 - Loop (+)
3 - Loop (-)
4 - Other devices
Bosch Security Systems, Inc. | 8/06 | F01U001402C
FMM-7045, FMM-7045-D | Installation Instructions | 3.0 Specifications
2
4
3
L
o
o
p
-
HUNDREDS
0
1
2
0
1
X X X
2
0
1
9
1
2
8
2
3
7
3
4
6
4
5
ONES
2.4
Mounting
The FMM-7045/FMM-7045-D mounts to a 3 in. x 2 in.
x 3½ in. device box (like a Steel City CXW) or a 4 in.
x 2 1/8 in. square box with a 5/8 in. mud ring (like the
Steel City 52171 box and 52-C-14-5/8 mud ring) with
the two provided screws. The multiplex single zone
input module should easily fit inside.
The back plate mounting holes on the FMM-
7045/FMM-7045-D can be accessed by opening the
key lock on the unit.
The FMM-7045/FMM-7045-D Pull Stations
are for indoor use only. If a pull station is
needed for outdoor use or in an unheated
area, an FMM-100 Series Pull Station rated
for the environment should be wired to a
multiplex module within the interior of the
building.

3.0 Specifications

Table 1: Specifications
Panel
Single Point
Programming
Type
Control Panel
D7024 or DS9400 Series FACP (with
Requirements
ROM version 2.0 or greater and a
D7039 or DS9431 Multiplex Expansion
Module installed). Refer to the D7024
Operation and Installation Guide (P/N:
31499) or the DS9400M/DS9400i
Installation Guide (P/N: 44578) for
specific programming information. Refer
to the D7039 Installation Instructions
(P/N: 38685) or the DS9431
Installation Instructions
41831) for multiplex wiring information.
Multiplex Bus
Alarm: 0.55 mA
Average Current
Standby: 0.55 mA
Draw
Optional
Replacement Glass Break Rods (FMM-
Equipment
100GR)
Operating
+32°F to +120°F (0°C to +49°C) non-
Temperature
condensing RH
Listings and
UL864
Approvals
CSFM
Nominal Bus
12 VDC
Voltage
(P/N:
3

Advertisement

loading

This manual is also suitable for:

Fmm-7045-d