Guide Specifications; Products; System Description; Quality Assurance - Carrier 38YCC Series Product Data

50 hz 10 seer export model sizes 18-60 1-1/2 to 5 nominal tons (7 to 17.5 kw)
Hide thumbs Also See for 38YCC Series:
Table of Contents

Advertisement

GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor- -mounted, air- -cooled, split- -system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air- -cooled coil, propeller- -type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

— Unit shall be manufactured in a facility registered to
ISO9001/BS5750 Part II, International Standard for
Quality Systems.
— Unit construction will comply with latest edition of
ANSI/ASHRAE and with NEC (U.S.A. Standard).
— Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500- -hr salt
spray test (U.S.A. Standard).
— Air- -cooled condenser coils will be leak tested at 150
psig (1034 KPa) and pressure tested at 300 psig (2068
KPa).
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is stored
and handled per unit manufacturer's recommendations.

PRODUCTS

Equipment
— Factory- -assembled, single- -piece, air- -cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
(R22), and special features required prior to field
start- -up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized,
prepainted steel.
Fans
— Condenser fan will be direct- -drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1- -phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of epoxy coated, enhanced
aluminum fins mechanically bonded to copper tubes
which are then cleaned, dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include liquid line
shutoff valve with sweat connections, vapor shutoff
valves with sweat connections, system charge of R- -22
refrigerant, compressor oil, accumulator, and reversing
valve.
Copyright 2007 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
AIR- -COOLED, SPLIT- -SYSTEM HEAT PUMP
Operating Characteristics
— The capacity of the unit will meet or exceed _____ Btuh
(_____ kW) at a suction temperature of _____ _F
(______C). The power consumption at full load will not
exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
(_____ kW) or greater at conditions of _____ CFM
(_____ L/S) entering air temperature at the evaporator at
_____ _F (______C) wet bulb and _____ _F
(______C) dry bulb, and air entering the unit at ____ _F
(______C).
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
_____ phase, 50 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
Printed in U.S.A.
Edition Date: 09/07
24
1- -1/2 TO 5 NOMINAL TONS (7 TO 17.5 kW)
Catalog No.38YCC ---C8PD
Replaces:38YCC--- C7PD
38YCC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents