Remote Thermostat Control
When connected to a remote thermostat, the indoor air
temperature sensing is shifted from the unit to the remote
thermostat. For this reason, the units will operate slightly
differently when connected to a remote thermostat. The
following chart shows the unit operation when connected to
a remote thermostat.
Feature
Indoor Frost Control
Freeze Sentinel
Auto Fan Speed
Electronic Temperature Limiting
Switch to Resistance Heat Based
On Indoor Temperature
Switch to Resistance Heat Based
On Outdoor Temperature
Reverse Cycle Defrost
Simultaneous Resistance Heat
with Heat Pump
Resistance Heat Lockout
"Smart Fan" Fan Cycle
Fan ON/AUTO Set On
Central Desk Control
Temperature Boost option should not be used with remote
thermostat operation since this will cause the unit to switch to
resistance heat when outdoor temperatures are below 46°F.
See RAK806 Universal Control cover Label on page 15.
Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units
ZONELINE
SERIES
2500
3500 and
5500
Thermostat wire size - up to 60 feet AWG20 - up to 66 feet AWG18
3500 Series
5500 Series
Yes
Yes
Yes
Yes
No
No
No
No
Determined by
Determined by
Remote Thermostat
Remote Thermostat
Yes
Yes
Yes
No
Yes
Fan ON/AUTO Set On
Remote Thermostat
Remote Thermostat
Yes
Yes
THERMOSTAT
MODEL
RAK163A1
Mechanical
RAK163D1
RAK163P1
Digital Programmable
RAK147
Mechanical
RAK147D1
RAK147P1
Digital Programmable
TYPE
FUNCTION
Digital
Cooling and Heating
Single Stage
Digital
Cooling
2 - Stage Heating
Common - Ground
White - Heater
Yellow - Compressor
Black - Not Used On 2500
Green - High Speed Fan
Green - Low Speed Fan
Red - 24 VAC
LOW
VOLTAGE
CONDUCTORS
4
5
5
6
6
6
17