What To Do If Something Unusual Occurs (Gt01/Gt11/ Gt21); Troubleshooting - Panasonic GT01 User Manual

Gt series programmable display
Hide thumbs Also See for GT01:
Table of Contents

Advertisement

5.1 What to DO If Something Unusual Occurs (GT01/GT11/
GT21)
Problem
Screen is
1) Power is not on.
blank
2) (When only lamp and message parts are
configured to the base screen) Value of
substitute reference device value does not
exist in substitute data.
Error code
An error has occurred in communication
[ER**]
between the GT and an external device (e.g.
appears at
PLC).
the top right
of the
screen
Screen
There is no base screen data in the GT.
displays [No
(Appears even when GT configuration data
Screen data]
exists.)
Screen
1) Screen settings from the PLC, the GT's
displays
switch part or the auto-paging indicate an
[Screen No.
unregistered screen number.
Error]
2) When bringing up the keyboard screen
during data input, an unregistered
keyboard screen number was specified.
3) GT configuration data and keyboard
screen data exist in the GT, but there is
no base screen data.
Screen
The total capacity of transferred base screen
displays
data exceeds the 384 kbyte capacity of the
[Memory is
GT.
Full]
An
1) The screen specification in the PLC
unspecified
screen setting, the GT switch part or the
screen
auto-paging is wrong.
appeared/th
2) The startup screen is specified in the GT
ere is
configuration settings (GTWIN).
trouble when
switching
screens.
3) An erroneous device or value is specified
in the first word of the basic
communication area word device.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Cause
Solution
1) Supply the power supply to unit as per
specifications.
2) Check the address of the substitute reference
device and the device values on the PLC side.
Refer to <5.3 Troubleshooting Error Codes>.
Transfer base screen data.
1) Create and register screen content or specify the
correct screen number.
2) Create and register keyboard screen or specify
the correct keyboard number.
3) Transfer base screen data from GTWIN.
Delete part of the base screen data so that the
capacity doesn't exceed the total capacity.
Data capacity can be checked by going to [View
(V)]→[Memory Usage Conditions] on GTWIN menu
bar. When the data capacity is not over the limit,
invalid data could possibly be remaining in the GT.
When transferring data, do so after deleting the
screen.
1) Specify the correct screen number.
2) Check the start-up screen setting for the GT
configuration settings in GTWIN. Delete
unnecessary settings and re-transfer
configuration data.
3) Check the device content specified on the PLC
side in the first word of the basic communication
area. (Do not use the basic communication area
with ladder programs.)