Kenmore 153.336941 Use & Care Manual page 42

30/40 gallon tall
Hide thumbs Also See for 153.336941:
Table of Contents

Advertisement

LED STATUS
PROBLEM
CORRECTIVE
ACTION
4 FLASHES
5 FLASHES
7 FLASHES
8 FLASHES
The
Gas
Control
Valve's
temperature
sensor has detected
that the water temperature was too
high. Once this condition occurs,
the Main Burner and the Pilot Light
wilt be shut off. Since the Pilot light
will be off, should
this condition
occur, this Flash
Code will only
be displayed
immediately
after
the Pilot has been relit. Turn Gas
Control Valve/Thermostat
knob to
OFF.
The
temperature
sensor
(thermistor) is defective.
Gas Control Valve failure.
This condition only appears if the
gas control/temperature
knob has
been turned off and the thermopite
continued
to
produce
electric
power.
This condition
can occur
if the thermopile
does
not cool
down as quickly as expected when
the unit is shut off. This condition
can also occur if the gas control/
temperature knob has been turned
off and
the
pilot
continues
to
operate because the pilot valve is
stuck in the open position.
Relight pilot and verify 4 flashes.
If 4 flashes are
observed, turn Gas Control Valve/Thermostat
knob
to OFF. Turn Main Gas Supply OFF. Replace the
Gas Control Valve/Thermostat.
See "Removing
and Replacing the Gas Control Valve/Thermostat."
Turn Gas Control Valve/Thermostat
knob to OFF.
Replace the temperature
sensor (thermistor).
Turn Gas Control Valve/Thermostat
knob to OFF.
Turn Main Gas Supply
OFF.
Replace
the Gas
Control
Valve/Thermostat.
See "Removing
and
Replacing the Gas Control Valve/Thermostat."
Make sure that the gas control valve/thermostat
knob is set to OFF.
Wait one minute. Remove
the outer door.
Look through the sight glass for
a pilot flame.
If a pilot flame is observed with the
gas control valve/thermostat
knob set to the OFF
position, the pilot valve is stuck open. Turn the main
gas supply OFF.
Replace the gas control valve/
thermostat.
For instructions,
see "Removing
and
Replacing the Gas Control Valve/Thermostat."
If the pilot flame
is not observed
when the gas
control valve/thermostat
knob is set to the OFF
position, wait 10 minutes for the thermopite to coot,
then attempt to relight the pilot by following
the
lighting instructions
on the water heater's label. If
this condition returns, replace the gas control valve/
thermostat.
See "Removing and Replacing the Gas
Control Valve/Thermostat"
for instructions.
42