C. Check "Operation selector" switch in the indoor unit.
: In case of wireless remote control unit (GS type)
• Has "Operation selector"
switch been set to ON
position ?
NO
Set "Operation selector"
switch to ON.
But neither unit runs.
Switch Ass'y or P.C.B.
Ass'y in the indoor unit
is defective.
D. Check compressor motor protectors.
a)
High pressure switch (63PH)
• Check high pressure switch.
Does high pressure switch
actuate ?
(63PH)
YES
• Is outdoor heat exchanger
coil dirty or are there
obstacles near air suction
inlet of outdoor unit ?
NO
• Check if outdoor fan rotates.
Refer to "Only outdoor fan
does not run."
b)
Compressor motor overcurrent relay (51C)
• Check compressor motor
overcurrent relay. (51C)
Does it actuate ?
YES
• Check power supply voltage.
Is voltage 90% or less of
rated voltage ?
NO
90% or more of
rated voltage.
• Following causes may be considered.
Locked rotor of compressor.
Overcharged refrigerant.
Air shortage of outdoor unit ventilation.
Obstacles in front of outdoor unit.
YES
Disconnect the socket from 2P (WHT) connector.
Check the continuity between No.1 and No.2 poles
of the socket.
YES
NO
Refer to "CHECKING ELECTRICAL COMPONENTS
(Electro magnetic contactor)".
Consult power supply company
YES
and restore voltage to
normal value.
– 59 –
4. Service procedures
IND. LAMP Ass'y or P.C.B.
Ass'y in the indoor unit
is defective.
0617_X_S
Clean heat exchanger coil
or remove obstacles.
0618_X_S
0619_X_S
SM830043