CONTROL CIRCUITS
or
02h
42h
31h
03h
1.
35h (ASCII hex) = 5H = 00000101
42h (ASCII hex) = Bh = 00001011
Note: 03h is the EXT character (end of transmission) and is
not part of the message.
2.
00000101 = 01010000
3.
01010000 + 00001011 = 01011011
4.
02h + 42h + 31h + 30h = A5h
5.
A5h + 5Bh = 100h
6.
The least significant byte is zero so the message and
LRC match.
Response or status bytes are sent from the TMS7 as an ASCII
string.
STX
[d1]h
[d2]h [d3]h
d1 =
30h
d2 =
30h
d3 =
30h plus upper nibble of status byte right shifted by four
binary places.
d4 =
30h plus lower nibble of status byte.
For example status byte = 1Fh, response is
STX
30h
30h
31h
Status bits (positive logic 1 = true)
Status
Function
Comment
Bit
Status.7
50 Hz
Only one of either Status.7 or
Status.6 can be at logic 1 when the
TMS7 is operating.
Status.6
60 Hz
Status.5
-
Unallocated
Status.4
Soft stop
Status.3
Positive
Will be at logic 0 when there is a
phase
negative phase rotation.
rotation
Status.2
-
Unallocated
Status.1
-
Unallocated
Status.0
-
Unallocated
Status_1 bits (negative logic 0 = true)
Status Bit
Function
NOT
-
Status_1.7
NOT
-
Status_1.6
NOT
-
Status_1.5
NOT
Restart
Status_1.4
Delay
NOT
Overload
Status_1.3
NOT
Run
Status_1.2
NOT
Output On
Status_1.1
NOT
Power On
Status_1.0
16
30h
35h
42h
[d4]h
LRC1 LRC2 ETX
3Fh
LRC1 LRC2 ETX
Comment
Motor is operating in an overload
condition.
Trip bits (negative logic 0 = true). The table below shows the
complement of these bits to give positive logic (1 = true).
Status Bit
Function
NOT Trip.7
Phase Loss
NOT Trip.6
Undercurrent
NOT Trip.5
Phase Rotation
NOT Trip.4
Overcurrent
NOT Trip.3
Over Temperature
NOT Trip.2
Installation
NOT Trip.1
Stall Protection
NOT Trip.0
Thermistor
ME00070B
TMS7 SERIES