Cleaning

On an annual basis, maintenance is required to ensure TrueDRY runs at peak efficiency.
Unplug TrueDRY DH65 before beginning ser-
1
vice. Grip and remove thumb screws (4 per
collar) and slide collars off.
Using a 1/2-in. hex drive or standard screw-
3
driver, remove the eight screws on either
side of the TrueDRY DH65. The side and
top panels can then be removed. Using a
damp cloth, wipe excess dust and debris
from blower, refrigerant coils, and compres-
sor coils. Reattach panels and collars when
finished.
69-2089EFS_D.indd 9
Grip filter tab at bottom to remove.
2
Replace with new filter.
M27334
Check the drain connection and drain line
4
to ensure it is clear of debris and sludge.
Ensure all hose connections are secure once
maintenance of the drain lines is complete.
When service is complete, initiate a call for
5
dehumidification and check that the com-
pressor and fan activate. If using the digital
VisionPRO IAQ or TrueIAQ controls, reset
maintenance reminders.
M27335
9
TrueDRY DH65
69-2089EFS—08