Diagnostics - Viessmann VITOPLEX 100?LS Installation And Service Instructions Manual

Typesxd, 0.26 to 0.7 t/h oil/gas fired boiler steam generator up to 1bar operating pressure
Hide thumbs Also See for VITOPLEX 100?LS:
Table of Contents

Advertisement

Troubleshooting

Diagnostics

Fault/
system characteristics
Burner does not start
Oxygen corrosion
(water side)
Flue gas temperature
too high
The safety valve
blows down
18
Cause
No voltage
Safety chain activated
Burner fault indicator
illuminates
Fuel supply interrupted
Remedy other faults in accordance with the burner
manufacturer's instructions
Topping up with
unsuitable water
Boiler is completely shut
down every day
Heat transfer is reduced
by contamination on the
flue gas and water side
Rated boiler output is
exceeded
Turbulators missing or
incorrectly installed
Blow−down pressure is
not identical with the
system pressure
Valve seat contaminated Clean the valve seat
Water trap pipe
(upstream of pressure
regulator) is clogged up
Remedy
Switch ON the mains
electrical isolator
Check all safety
equipment
Press the reset button at
the burner control unit
Open the shut−off valves
in the fuel supply line
and filter
Check water treatment
system and injection
equipment in
accordance with VdTÜV
[or local] guidelines
Switch to standby
(95 ºC) instead of a
complete shutdown
Clean the boiler
Check the rated burner
output
Carry out maintenance
and installation in acc.
with page 10 and 12
Check the operating
pressure with a suitable
pressure gauge
Clean pipes