Location and Leveling Water Supply and Drain Connections Final Checklist Installation Practice F20 and F40 Technical Data and Operating Instructions F60 and F85 Technical Data and Operating Instructions Cleaning/Rinsing For F20, F40, F60, F85 F20 F40, F60 F85, Wiring Diagrams Technical Specification R22 Machines FCI 20, 30, 40, 60, 85...
General Information and Installation Instructions Introduction The Electronic Cubers are quality designed, engineered and manufactured. Their ice making systems are thoroughly tested providing the utmost in flexibility to fit the needs of a particular user. These icemakers have been engineered to our own rigid safety and performance standards. The VDE –...
fittings and a shut off valve installed in an accessible position between the water supply line and the unit. WATER SUPPLY - WATER COOLED MODELS. The water cooled versions require two separate inlet water supplies on models 40 and 60, one to supply water for the ice production and one for the water cooled condenser.
F20 and F40 Technical Data and Operating Instructions Technical Data Model Output – kg/24hr Bin storage capacity – kg Cubes per cycle Cubes kg per cycle Cycle time – minutes Amps start/run Watts consumption (30°C Ambient Temp) Water consumption (Water Temp at 15°C Ambient Temp 21°C)
F60 and F85 Technical Data and Operating Instructions Technical Data Model Output – kg/24hr Bin storage capacity – kg Cubes per cycle Cubes kg per cycle Cycle time – minutes Amps start/run Watts consumption (30°C Ambient Temp) Water consumption (Water Temp at 15°C Air Temp 21°C) Refrigerant Refrigerant charge grams Evaporator Temp with Gas Pressure at 10.5 Bar ( Ambient Temp 21°C)
Decreasing the defrost time will increase the freeze time so adjustments to the cube size thermostat may need to be made to decrease the freeze temperature. Cleaning/Rinsing For F20, 40, 60, 85 Remove the bottom front panel and locate the changeover switch.
COMPRESSOR, WATER INLET SOLENOID VALVE, HOT GAS VALVE NOTE: The length of the defrost cycle is (non-adjustable) automatically determined by the microprocessor of The P.C. BOARD in relation to the time T2 necessary for the unit to reduce the evaporator temperature from 0˚C (35˚F) to -1 3˚C (8.5˚F) and of the ambient temperature, as illustrated in Table C.
Page 11
7. The DIP. SWITCH keys setting is made in consideration of the model and of the type of condenser used (air or water cooled). In Table B, page 12, are indicated the various lengths of the third portion of freezing cycle (Time mode) in accordance with the different combinations of the DIP.
Page 12
ICE BIN LEVEL SENSOR The ice bin level temperature sensor, secured to one of the storage bin walls, stops the operation of the entire ice maker at the end of the defrost cycle when its sensing probe (in contact with the stored ice) reaches the temperature of +2˚C (35˚F) lighting up, in the meantime, the third RED LED.
Page 13
Dip Switch Positions Table A SWITCHES FCI 20 FCI 30 FCI 40 Table B LENGTHS OF TIMED PORTION OF FREEZING CYCLE Ta ACCORDING TO THE DIP SWITCH SETTING COMBINATIONS Dip Switch Settings FCI 20 and FCI 30 - R134A Machines IT IS IMPORTANT TO NOTE THAT THE OPERATING INSTRUCTION AND PRINCIPLE OF OPERATION FOR THE FCI 20 AND FCI 30 ARE THE SAME AS THE R22 MACHINES Dip switch...
Technical Specification - R134A Machines MODEL Output – kg/24hr. Ice prod. per cycle Freeze time cycle 19.5 min Cubes per cycle Bin capacity kg Electrical Supply 230/1/50 Hz Amp start / run 11amp/2amp Fuse rating Watts consumption (30°C ambient) Water consumption 7.5 litre per hr Min evap Temp °C Heat rejection watts...
Page 16
At completion of the water filling phase (5 minutes) the unit passes automatically into the freezing cycle with the start up of: COMPRESSOR WATER PUMP FAN MOTOR (in air cooled version) controlled by the condensing temperature sensor located within the condenser fins (Fig.2). Page 20. 10.2 Operational Checks Install, if necessary, the refrigerant service gauges on both the high side and low side Schräder valves to check the compressor head and suction pressures.
Principle of Operation 11.1 How it works In the cube ice makers the water used to make the ice is kept constantly in circulation by an electric water pump which primes it to the spray system nozzles from where it is diverted into the inverted mould cups of the evaporator. A small quantity of the sprayed water freezes into ice; the rest of it cascades by gravity into the sump assembly below for recirculation.
ambient temperature as detailed in Table C. Page 18. The electrical components in operation during this phase are: COMPRESSOR WATER PUMP WATER INLET SOLENOID VALVE HOT GAS SOLENOID VALVE The incoming water, passing through the water inlet valve and the flow control, runs over the evaporator platen and then flows by gravity through the dribbler holes down into the sump/reservoir.
the service and inspection operations. IN OPERATION: The unit is running through the freezing and defrost cycle stopping automatically only at full bin situation. RE-SET/HI TEMPERATURE: To be selected to resume the unit operation when the ice maker shuts off due to the intervention of the condenser temperature sensor (too high condensing temperature).
Wiring Diagram WIRING DIAGRAM - SCHEMA ELETTRICO SCHÉMA ÉLECTRIQUE - SCHALTUNGSCHEMA AIR & WATER COOLED - RAFFREDDAMENTO AD ARIA ED AD ACQUA. REFROIDISSEMENT A AIR ET A EAU - LUFT UND WASSERGEKÜHLT Printed Circuit Board Fuse Rinsing Freezing Oper. Too High Temperature Bin Full Power On Reset to High Temp.
Circuit Board and Component Sequence of Operation Fig./ABB 1 START UP Fig./ABB 3 LED BLINKING EVAPORATOR TEMPERATURE HIGH LED CONSTANT CONDENSER TEMPERATURE HIGH Fig./ABB 5 DEFROST CYCLE Fig./ABB 7 STAND BY COMPRESSOR ICE LEVEL SENSOR SENSORS EVAP. TEMPERATURE COND. TEMPERATURE AMBIENT TEMP.
Maintenance and Cleaning Instructions 16.1 General The periods and the procedures for maintenance and cleaning are given as guides and are not to be construed as absolute or invariable. Cleaning, especially, will vary depending upon local water and ambient conditions and the ice volume produced; and, each ice maker must be maintained individually, in accordance with its particular.
Page 23
Fig. 11 6. (R134A Machines Fig. 8) NOTE With the system in CLEANING/RINSING mode the water pump is the only component in operation to circulate the cleaning solution in entire water system. 7. Let the unit remain in the CLEANING/RINSING mode for about 20 minutes then turn the program selector on STAND BY again. 8.