Water Valve Pressure Drop - Amana HVK03E Installation Instructions Manual

Ptac hydronic heat kit
Table of Contents

Advertisement

2-Way Valve
ERIE Models: 654C*
VT/S22*
Water
Pressure Drop
GPM
(psig)
1.00
0.16
1.13
0.20
1.25
0.25
1.38
0.30
1.50
0.36
1.63
0.43
1.75
0.49
1.88
0.57
2.00
0.64
2.13
0.73
2.25
0.81
2.38
0.91
2.50
1.00
2.63
1.11
2.75
1.21
CV=2.5
Dimensions of Complete Installation
Top of Wall Sleeve
4-1/8"
16-1/16"
Bottom of Wall Sleeve
Figure 20
Side View

Water Valve Pressure Drop

3-Way Valve Bypass
ERIE Models: 654C*
Water
Pressure Drop
GPM
(psig)
1.00
0.11
1.13
0.14
1.25
0.17
1.38
0.21
1.50
0.25
1.63
0.30
1.75
0.34
1.88
0.39
2.00
0.44
2.13
0.50
2.25
0.56
2.38
0.63
2.50
0.69
2.63
0.77
2.75
0.84
CV=3.0
Pd
Q = CV
Q = Flow in Gallons/Min
CV = Flow Coefficient of Valve
Pd = Pressure Drop (psig)
9-7/8"
3"
Hydronic Front
Toe Plate
0" - 3.0" Long
is a registered trademark of Maytag Corporation or its related companies and is used under
license to Goodman Company, L.P., Houston, TX. All rights reserved.
Goodman Company, L.P.
5151 San Felipe, Suite 500 • Houston, TX 77056
www.amana-ptac.com
© 2010 - 2011 Goodman Company, L.P.
3-Way Valve Service
ERIE Models: 654C*
Water
Pressure Drop
GPM
(psig)
1.00
0.04
1.13
0.05
1.25
0.06
1.38
0.08
1.50
0.09
1.63
0.11
1.75
0.12
1.88
0.14
2.00
0.16
2.13
0.18
2.25
0.20
2.38
0.23
2.50
0.25
2.63
0.28
2.75
0.30
CV=5.0
5-1/2"
Hydronic Air
Discharge
12
3-Way Valve Bypass
and Service
ERIE Models: VT32*
Water
Pressure Drop
GPM
1.00
1.13
1.25
1.38
1.50
1.63
1.75
1.88
2.00
2.13
2.25
2.38
2.50
2.63
2.75
CV=4.0
42"
PTAC Unit Wall Sleeve
Figure 21
Top View
(psig)
0.06
0.08
0.10
0.12
0.14
0.17
0.19
0.22
0.25
0.28
0.32
0.35
0.39
0.43
0.47

Advertisement