Q345A, Q348A, Q348B, Q362A,Q373A
and Q381A Pilot Burner/Igniter-Sensors
These pilot burner/igniter-sensors provide pilot flame
ignition and sensing in intermittent pilot systems. They
consist of a target type pilot burner with a combination
spark igniter and flame sensor mounted in place of the
thermocouple.
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to
follow instructions can damage product or cause a
hazardous condition.
2. Check ratings given in instructions and on
product to make sure product is suitable for your
application.
3. Make sure installer is a trained, experienced
service technician.
4. After completing installation, use these
instructions to check out product operation.
WARNING
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Follow these warnings exactly:
1. Disconnect power supply before wiring
to prevent electrical shock or equipment
damage.
2. To avoid dangerous accumulation of fuel
gas, turn off gas supply at appliance service
valve before starting installation and
perform Gas Leak Test after completion of
installation.
3. Do not bend pilot tubing at the control or
pilot after compression nut has been
tightened. Gas leakage at the connection may
result.
Follow appliance manufacturer instructions if avail-
able; otherwise, use instructions provided below.
LOCATION
1. Position pilot burner/igniter-sensor for easy
access and observation. In replacement applications,
replace pilot burner/igniter-sensor with an identical unit
and position new pilot burner/igniter-sensor in the same
location and orientation as the original one.
Application
Installation
G. S. • Rev. 7-93 • ©Honeywell Inc. 1993 • Form Number 60-0653—8
Fig. 1—Mount pilot burner/igniter-sensor on
main burner.
PILOT BURNER/IGNITER-SENSOR
MUST BE RIGIDLY POSITIONED
RELATIVE TO MAIN BURNER
Fig. 2—Location of pilot burner/igniter-sensor.
PILOT BURNER/
IGNITER-
SENSOR
JUST RIGHT
IGNITION FLAME
JUST MISSES
MAIN BURNER
2. Mount pilot burner/igniter-sensor on main burner.
Mounting surfaces other than the main burner may shift,
bend, or warp as furnace expands and contracts while
operating. See Fig. 1.
3. Mount pilot burner/igniter-sensor so the pilot flame
remains properly positioned with respect to the main
burner flame. See Fig. 2.
4. Supply pilot flame with ample air free of
combustion products.
5. Do not impinge pilot flame on adjacent parts.
Do not impinge main burner flame on pilot burner/
igniter-sensor.
6. Do not expose pilot flame to falling scale, which
could impair main burner ignition.
7. Do not expose pilot burner/igniter-sensor to main
burner rollout while igniting or extinguishing.
8. Do not expose pilot flame to drafts that push or
pull pilot flame away from the igniter-sensor.
NOTE: The Q381A Pilot Burner/Igniter-Sensor is for
horizontal mounting only. Mounting bracket must
remain vertical.
M3271
PILOT BURNER/
PILOT BURNER/
IGNITER-
IGNITER-
SENSOR
SENSOR
TOO HIGH
TOO LOW
IGNITION
MAIN BURNER
FLAME WILL
FLAME WILL
IMPINGE ON
IMPINGE ON
MAIN BURNER
IGNITION-
SENSOR
M3273

Advertisement

loading

Summary of Contents for Honeywell Q348A

  • Page 1 NOTE: The Q381A Pilot Burner/Igniter-Sensor is for and position new pilot burner/igniter-sensor in the same horizontal mounting only. Mounting bracket must location and orientation as the original one. remain vertical. G. S. • Rev. 7-93 • ©Honeywell Inc. 1993 • Form Number 60-0653—8...
  • Page 2: Startup And Checkout

    2. A male 1/4 in. [6 mm] quick-connect terminal is 2. Paint pipe connections upstream of pilot burner provided on Honeywell ignition modules. Fasten female with rich soap and water solution. Bubbles indicate gas quick-connect to wire end at ignition module.
  • Page 3 TYPICAL M1273 SHIELD IGNITER-SENSOR Set the thermostat to call for heat. Q345A, Q348A-B, Q362A AND Q 381A M3777 Watch the pilot burner during the ignition sequence. See if: • Ignition spark continues after the pilot is lit. • The pilot lights and the spark stops, but main ADJUST PILOT FLAME burner does not light.
  • Page 4 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, Minnesota 55422 Scarborough, Ontario M1P 2V9 QUALITY IS KEY...

This manual is also suitable for:

Q348bQ362aQ373aQ381aQ345a