Lcd Display With All Possible Elements Shown; Lcd Display Showing Default Screen; Power-Up; Installer Setup (Is) Mode - Honeywell SUITEPRO TB6575 Installation Instructions Manual

Digital fan coil thermostats
Hide thumbs Also See for SUITEPRO TB6575:
Table of Contents

Advertisement

TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
Fig. 21. Removing the thermostat.
SETUP
The thermostat provides an LCD display, two buttons
below the display for System and Fan control and two
adjustment buttons (Up and Down) to the right of the
display. See Fig. 23.
Settings, including setpoints, are permanently retained in
EEPROM in case of a power outage.
Fig. 22 illustrates all the possible LCD display elements.
Only those elements pertinent to the current settings and
status (including the text for the two buttons, System and
Fan), actually display.
Freeze Set to
Locked
Protect Setup
Set to RoomTemp
Pipe
Sensor
Heat On Cool On
OffHeatAutoCool
Fig. 22. LCD display with all possible elements
62-0278—07
ºF ºC
Test
ºF ºC
Economy
Setback
Fan On
LowMedHiAuto
M27584
shown.
M27592
Fig. 23. LCD display showing default screen.

Power-up

At power-up, the thermostat's LCD shows all display
segments for two seconds, enters a self-test mode for a
few seconds, and then displays the current room
temperature (default screen), as shown in Fig. 23.
NOTE: If there is a temperature sensor failure or the
temperature is outside of the operating
range, the room temperature display shows
two dashes,
When the sensor returns to its operating
range, the temperature display resumes.
CAUTION
Equipment damage hazard.
Power overload will damage the thermostat.
The thermostat has a safety fuse rated at 15 A/
250 Vac. If the fuse blows, the thermostat must be
replaced. The fuse is not field replaceable.
This fuse is provided as a safety feature to prevent
fire if the thermostat is overloaded.

Installer Setup (IS) Mode

To enter Installer Setup Mode:
• Press and hold both the System button (labeled
Heat/Cool) and the Up Arrow button for three (3)
seconds.
This displays the setup screen on the LCD. See Fig. 24.
NOTE: Exiting Installer Setup Mode is the same as
the method for entering setup mode.
Table 4 provides the setup codes (IS codes) and values.
To enter the setup parameters:
1. Press the System (Heat/Cool) button to cycle
through the IS codes, which display in the upper
right following the word Setup.
2. Press the Up or Down Arrow buttons to cycle
through the option values for the currently displayed
IS code. The values display in the center of the
screen.
3. After the desired value displays, press the System
button to store your value selection and display the
next IS code.
10
Set to
RoomTemp
ºF
Heat On
Fan On
Heat
System
Fan
SYSTEM
BUTTON
.
— —
UP AND DOWN
ARROW BUTTONS
ºF
Auto
M27586
FAN
BUTTON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents