Specifications; Ordering Information - Honeywell T7984 A Product Data

Electronic modulating control thermostats
Table of Contents

Advertisement

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS

SPECIFICATIONS

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not
exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions,
and some minor differences in performance can be expected if those conditions are changed.
MODELS: T7984A,B,C, 2 to 10 Vdc analog output
Model
Output 1
T7984A
Modulating 2 to
10 Vdc
T7984B
Modulating 2 to
10 Vdc
T7984C
Modulating 2 to
10 Vdc
* Remote sensor models are:
272845 Remote wall mount sensor
272847 Remote duct mount sensor
DIMENSIONS
See Figure 1.
MOUNTING: Mounts to single-gang NEMA-standard 2"x 4"
electrical box, or directly to wall requires 1 1/8" [35„mm]
access hole for wiring.
WIRING: Four to eight 1/8" screw terminals suitable for 2 no.
18 AWG [1 mm 2] wires each depending on model.
POWER SUPPLY: 19-30 Vac, 50-60 Hz, 2 VA, Class 2. (Does
not include actuator or reheat stage power requirements.)
OPERATING AMBIENT:
32-104°F [0-40°C] at 5-95% Relative Humidity (non-
condensing).
ACCURACY: 1°F (0.6°C) PRECISION: ±1°F (0.5°C) tempera-
ture after stabilization.
PRECISION: ±1°F (0.5°C) temperature after stabilization.
SETPOINT RANGE: 55-90°F [13-32°C], T7984A.
Heating: 55-75°F [13-24°C], T7984B, C*.
Cooling: 75-90°F [24-32°C], T7984B, C*.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
95C-10815–2
Table 1. Model Specifications
Cool/Heat
Changeover
For Output 1
Output 2
Dry Contact or
On/off
Sensor
-
-
Dry Contact or
Modulating 2 to
Sensor
10 Vdc
2
Night Setback
-
Internal or
remote
Dry Contact
Internal or
remote
Dry Contact
Internal or
remote
* The maximum heating setpoint and minimum cooling
setpoint is electronically limited to 75°F [24°C].
REMOTE SENSOR: 47 kΩ NTC thermistor [part nos. 272845
and 272847].
ANALOG OUTPUT: 2 to 10 Vdc, 2 mA max.
SWITCHED OUTPUT RATING: 0.5A running, 1.1A inrush,
24Vac, protected with selfresetting fuse.
OPERATING PARAMETERS: See Table 2 for installer selections.
APPROVALS:
Designed for Class II low voltage installation only.
Case and cover meets UL„94-5V flammability requirements,
and North American codes for line voltage thermostat
enclosures.
Meets requirements of F.C.C. Part 15 Class B, IEC 801-3 for
radio frequency interference.
ACCESSORIES:
272845 - Remote sensor (wall mounted).
272846 - Adaptor plate for 2-gang NEMA, or British 75 mm
electrical box.
272847 - Remote sensor (duct mounted).
Main
Temperature
Mode Selection
Sensor *
Input
-
Jumper
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T7984 bT7984 c