Wheelock POWERPATH PS-12/24-8MP Installation Instructions Manual page 14

Power booster
Hide thumbs Also See for POWERPATH PS-12/24-8MP:
Table of Contents

Advertisement

Example 5: IN>OUT SYNC MODE with External Sync Module with Audible Silence
(CLASS B)
SM/DSM
+ OUT1
F
+ IN1
MINUS 1
A
+ AUDIBLE
EOLR
C
- AUDIBLE
P
NOTE:
When using the Wheelock external Sync Module (SM or DSM), synchronization will only occur with
Wheelock sync appliances.
Example 6: WHEELOCK SYNC MODE without Audible Silence (CLASS B)
F
A
C
P
This mode will only synchronize Wheelock horns, horn strobes, and strobes with the synchronization capability.
If only strobes are connected to the POWERPATH outputs, the initiating input to IN2 is not required.
When synchronized horns are used on the two wire output of the POWERPATH, IN2 must be connected as
shown or the horns will not operate.
P84333 K
OUT1-4
IN>OUT SYNC
+
IN1
WHEELOCK SYNC
-
TEMPORAL
INPUT SELECT
TO NEXT
ON
ON
ON
APPLIANCE
OR EOLR
+
RET1
-
POWERPATH
SW9
OUT1-4
+
IN1
IN>OUT SYNC
-
WHEELOCK SYNC
TEMPORAL
INPUT SELECT
ON
ON
ON
-
RET1
+
POWERPATH
+
IN2
-
+
TO NEXT APPLIANCE
RET2
OR EOLR
-
SW9
+
OUT1
-
EOLR
+
OUT2
2.2K OHMS
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
+
OUT1
-
EOLR
+
OUT2
2.2K OHMS
-
EOLR
+
OUT3
2.2K OHMS
-
EOLR
+
OUT4
2.2K OHMS
-
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
TO NEXT APPLIANCE
OR EOLR
(2.2K OHMS)
Sheet 14 of 23