7800 SERIES EC7895A, RM7895A RELAY MODULE
Environmental Ratings:
Ambient Temperature:
Operating: -40° F to 140° F.
Storage: -60° F to 150° F.
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
Refer to Fig. 1 and 2.
Plug-in Flame Signal Amplifiers
Type
Color
Rectification
Green
Infrared
Red
Ultraviolet
Purple
Blue
a
Order flame rod separately; see holder Instructions.
b
Use only Honeywell Photocell, part no. 38316.
c
The C7012A,C, C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once
every twenty-four hours. Appliances with burners that remain on continuously for twenty-four hours or longer should use the
C7012E,F Flame Detector with the R7847C Amplifier or the C7076A,D Flame Detector with the R7886A Amplifier or the C7061
Flame detector with the R7861 Amplifier as the ultraviolet flame detection system.
d
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the burner if the
amplifier fails.
e
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner
operation and shuts down the burner if the detection system fails.
f
When R7861 is used with EC7895, the application requires a step down transformer. See Fig. 14.
g
Use with RM7895A only.
65-0205
Table 2. Flame detection systems (Figs. 3, 4, 5).
Self-
Checking
Model
No
R7847A
No
R7847A
No
R7847A
d
Dynamic
R7847B
AMPLI-
CHECK®
d
Dynamic
R7847B
AMPLI-
CHECK®
d
Dynamic
R7847B
AMPLI-
CHECK®
e
Dynamic
R7847C
Self-Check
No
R7848A
d
Dynamic
R7848B
AMPLI-
CHECK®
No
R7849A
d
Dynamic
R7849B
AMPLI-
CHECK®
Dynamic
R7861A
f
Self-Check
e
Dynamic
R7886A
g
Self-Check
Weight:
RM7895 with Dust Cover: 1 pound 15 ounces, unpacked.
IMPORTANT
Flame Detection System available for use with
EC7895 and RM7895. To select your Plug-in Flame
Signal Amplifier and applicable Flame Detector, see
Table 2 and Fig. 3 through 5.
Applicable Flame Detectors
Flame
Failure
Response
Time
Fuel
.8 or 3 sec
Gas
Rectifying Flame
Rod Holders
.8 or 3 sec
Oil
Rectifying
Photocell
3 sec
Gas,
Ultraviolet
Oil, Coal
(Purple Peeper)
.8 or 3 sec
Gas
Rectifying Flame
Rod Holders
.8 or 3 sec
Oil
Rectifying
Photocell
3 sec
Gas,
Ultraviolet
Oil, Coal
(Purple Peeper)
3 sec
Gas,
Ultraviolet
Oil, Coal
(Purple Peeper)
3 sec
Gas,
Infrared
Oil, Coal
(Lead Sulfide)
3 sec
Gas,
Infrared
Oil, Coal
(Lead Sulfide)
.8 or 3 sec
Gas, Oil
Ultraviolet
(MiniPeeper)
.8 or 3 sec
Gas, Oil
Ultraviolet
(MiniPeeper)
3 sec
Gas,
Ultraviolet
Oil, Coal
3 sec
Gas,
Ultraviolet
Oil, Coal
(Adjustable
Sensitivity)
4
Type
Models
C7004, C7007, C7011
a
Complete Assemblies:
C7008, C7009, Q179.
C7003, C7010, C7013,
b
C7014
c
C7012A,C.
C7004, C7007, C7011
a
Complete Assemblies:
C7008, C7009, Q179.
C7003, C7010, C7013,
b
C7014
c
C7012A,C.
C7012E,F.
C7015
C7015
C7027, C7035,
c
C7044.
C7027, C7035,
c
C7044.
C7061
C7076