HITACHI INVERTER
J300 SERIES
QUICK REFERENCE GUIDE (Part 1/2)
Three phase input 400V
Monitor (LED-Display)
This display shows frequency,
motor current, voltage, motor
direction, and other parameters.
FUNC-Taste
Power Lamp
This key is used to
Power Lamp of
select parameters
POW ER
Control Circuit
and for storing
modified
parameters.
FUNC .
$% !
RUN
#$%
RUN Key
This key is used for
starting using the
direction set by F 4 .
STOP/
key
(When terminal run
RESET
This key is used for
is selected this key
does not function).
stopping the motor or
resetting errors or trips.
Operation procedure (example for the digital operator)
000
FUNC .
d 0
F 4
FUNC .
(7 x)
Turn power
on.
If reverse run ( r ) is on, forward
run ( F ) can be selected using
the UP or DOWN key.
Starting command and set value via
digital operator (instead of terminals)
Data is
stored
(3 x)
F 9
00
03
FUNC .
FUNC .
(5 x)
F 2
0.0
60.0
FUNC
FUNC
Press con-
tinuously
Start run
Setting frequency to 60Hz
(Motor operates)
Monitoring actual
output frequency
60.0
FUNC
3
[FUNC key] ... This key switches
FUNC .
between the parameter area, data
area, and extended function area.
Each time the key is pressed, the
display changes as follows:
d 0
d 1
d 2
d 3
d10
UP/+ Key,
DOWN/- Key
These keys are
d11
used to change
data and
F 2
parameters.
r
[START key] ... This key
starts the J300 inverter.
RUN
Set forward or reverse
run using F 4 .
F
Data is
FUNC
Setting extended functions
stored
FUNC .
F 4
F14
FUNC .
(4 x)
Extended functions are
entered from F14
F 9
using the FUNC key.
Following this, the
function parameter
Data is
stored
number is displayed for
which data had been
entered last.
After changes to data
have been made, the
FUNC key must be
RUN
pressed. When the
FUNC key is being
pressed once more,
F 2
control is returned back
to A - - .
(6 x)
Explanation of display at power on
d 0
When the inverter is turned on, the display returns to what was displayed when the power
was last turned off (except in the extended function mode).
30.1
30.0
F 6
FUNC
F 6
FUNC
After the data has
been changed,
press the FUNC
key to save data.
29.9
[UP key, DOWN key] ... These keys change the
values of data area, and parameters:
Output frequency
Set the motor
F 4
monitor
direction
Motor revolution
Set acceleration
F 6
monitor
time
Set deceleration
Output current
F 7
time
monitor
Manual boost
Scaled output
F 8
configuration
frequency monitor
Control mode
F 9
Trip monitor
configuration
FM signal
Trip history
F10
adjustment
monitor
Motor voltage
Output frequency
F11
AVR function
monitor / setting
Extended
F14
functions
[STOP key] ... This key
stops the J300 inverter.
$% !
#$%

When a trip occurs, this key
becomes the RESET key
Extended function
parameter number
A 0
When an extended function is to be used, select the
extended function group
F14
by using the two
keys
and
so as to enter the extended
A 1
function mode.
Extended function data.
A96
0
200
FUNC .
FUNC .
Return to extended
function parameter
and memorize
4
Protective Functions
The SJ100 series inverter will trip on overcurrent, overvoltage and undervoltage to protect the
inverter.The output is shut down and the motor runs free. This condition is held until it is reset.
Trip
Contents
Overcurrent
When the output of the inverter is short circuited,
protection
the motor is locked, or a heavy load is suddenly
applied, and the inverter output current exceeds a
predetermined level, the inverter is shut off.
Overload
When a motor overload is detected by the electronic
protection
thermal function, the inverter is shut off.
Braking resis-
When regenerative braking resistor exceeds the usage
tor overload
time duration an overvoltage caused by the stop of the
BRD function is detected, and inverter output is cut off.
Overvoltage
When the inverter DC bus voltage exceeds a pre-
protection
determined level due to regenerative energy from the
motor, this trip occures and the inverter is shut off.
EEPROM error
When the inverter memory has a problem due to
(NOTE 1)
noise or excessive temperature rise, this trip occurs
and the inverter is shut off.
Undervoltage
A decrease of DC bus voltage may result in improper
protection
function of the control unit. It may also cause motor
heating and low torque. The inverter is shut off when
the DC bus voltage goes below a certain level.
CT error
When a large noise source is near the inverter or an
abnormality occurs on built-in CT, inverter output is
cut off.
CPU error
Malfunction or abnormality of the CPU. The inverter
is shut off.
External trip
A trip signal from external equipment shuts off the
inverter. It is necessary to assign the external trip to
an intelligent terminal.
USP error
Indicates an error when power is turned on while the
inverter run is enabled (with USP function selected).
Ground fault
The inverter is protected by detection of ground
protection
faults between the drive output and the motor at
power on. Protection is for the inverter only and not
for humans.
Input
When the input voltage is higher than a specified
overvoltage
value, it is detected and 100 seconds after power is
turned on, the inverter is shut off.
Short power
A short input voltage interruption (>15ms) occured.
down
The inverter is shut off.
Error in link to
There is an error in the link to the extension card in
option 1
slot 1 (2). The inverter is shut off.
(option 2)
Error option 1
There is an error in the extension card in slot 1 (2).
(option 2)
The inverter is shut off.
Phase failure
One of the power supply phases has broken down.
The inverter is shut off.
J300 data setting values
J300 inverters provide many functions whose parameters can be
set by the user. It is recommended that the parameters that have been set by the user be recorded
in order to speed the
investigation and re-
J300
pair in the event of
a failure.
Mfg.No.
Drive keypad display sequence
Standard Setting
Display
Function
d 0 .. d 3
Display functions
d10, d11
F 2
Set output frequency (Hz)
F 4
Set motor direction
F (forward)
F 6
Acceleration time (s)
F 7
Deceleration time (s)
F 8
Configure manual boost
F 9
Configure control mode
F10
FM signal adjustment
F11
Motor voltage AVR function
F14
Extended function group
Refer to pages 6 and 7
5
Display
Const. speed: E 1/ 31
At decelerat.: E 2/ 32
At accelerat.: E 3/ 33
At the others: E 4/ 34
E05
E06
E07
E08
E09
E10
E1 1
E12
E13
E14
E15
Slot 1: E17
Slot 2: E18
Slot 1: E19
Slot 2: E20
E24
This information is written on
the nameplate located on one of
the sides of the J300 inverter.
Set Value
Refer to page 4
0.0
30.0
30.0
31
03
72
380