B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm)
the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a
DVP-HSM-B will be required.
15-1/8 in.
(384 mm)
12 in.
(305 mm)
Figure 16.7 SLP Series Vent Components
76
8 in.
(203 mm)
SLP-TRAP2
Horizontal Termination Cap
DVP-FBHT
SL-2DVP
SLP90
Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13
Heat
Shield
Term Cap
Max
Effective
Trap2
Length
SLP-TVHW
Vertical
Termination Cap
Minimum
Maximum
Effective Length
Effective Length
5-1/4 in.
9-1/4 in.
133 mm
235 mm
DVP-FBHT