Top Vent - Horizontal Termination
V
Minimum
1
Elbow only
1 ft.
305 mm
2 ft.
610 mm
3 ft.
914 mm
4 ft.
1.22 m
10 ft.
5 ft.
1.52 m
16 ft.
V
+ H
= 30 ft. (9.14 m) Maximum
1
1
Note: A 6 in. (152 mm) section of straight flue must
be attached to the heater before a 90° elbow.
USE SLP SERIES COMPONENTS ONLY
Figure 7.4
H
Maximum
1
NOT ALLOWED
2 ft.
610 mm
4 ft.
1.22 m
8 ft.
2.44 m
3.05 m
4.88 m
Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2 /13
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling firestops.
• ALWAYS maintain specified clearances around
• Install wall shield and ceiling firestops as speci-
Failure to keep insulation or other material away
from vent pipe may cause fire.
Example: DVP pipe 3 ft. (1 m) min. vertical = 11 ft. (3.35 m)
max. horizontal
SLP pipe 7 ft. (2.13 m) min. vertical = 11 ft. (3.35
m) max. horizontal
H
1
WARNING
venting and firestop systems.
fied.
V
1
27