Jumper Setting Summary - Salus PL07 Instruction Manual

Pump and boiler logic module
Table of Contents

Advertisement

Salus PL07 Manual Ver007.qxd:Layout 1

JUMPER SETTING SUMMARY

Jumper
J1 – Boiler and Pump
protection ON – OFF
J2 – Pump overrun
time ON – OFF
10
Function
OFF – Disables boiler
and pump protection
(immediately turns pump
and boiler relays on when a
thermostat calls for heat).
ON – Enables boiler and
pump protection (delays
turning on pump and boiler
relays for 3 minutes when
a thermostat calls for heat).
ON – After all thermostats
have switched off the pump
runs for an additional 3
minutes for boiler protection.
OFF – Disables pump over run.
When all thermostats are
switched off the pump will also
switch off immediately as well.
PL07 INSTRUCTION MANUAL
10/9/10
Default Setting
Jumper in ON position
Jumper in ON (3
minute) position
10:03