Weil-McLain GOLD CGI 2 SERIES Manual page 24

Gas-fired water boilers gold cgi series 2
Hide thumbs Also See for GOLD CGI 2 SERIES:
Table of Contents

Advertisement

GOLD CGi Gas-Fired Water Boiler — Boiler Manual
4d
Piping — low temperature systems
Primary/secondary
bypass piping method
Primary/secondary
the flow rate and temperature drop in the heating
circuit(s) is determined only by the heating circuit
circulator(s). So adjustment of the bypass valves in
the boiler circuit will not cause a change in the heating
circuit rate and temperature distribution.
Figures 20 and 21
primary/secondary
using
for low temperature systems such as
systems
tives, see pages 6 through 9.
The bypass valves (items
hot boiler outlet water with cooler system return water
— set to assure a minimum return water temperature
(at least 130°F) to the boiler. Set the valves as explained
below.
Temperature gauges
Gauge
4a
4b
Gauge
but
required
4
(preferred)
bypass piping is preferred because
show suggested bypass arrangements
bypass piping (preferred)
converted gravity systems
or
7a
and
7b
) provide mixing of
is suggested, but optional on any system.
is optional on converted gravity systems,
on radiant heating systems — to display
prevent low return water temperature
Failure to
the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of
water temperature
tion pumping control
Boiler return water temperature will be adequately controlled using the methods shown
in this manual provided the
DO NOT
apply the methods of this manual if the system is equipped with an
reset control.
Instead,
turn water temperature
Contact your Weil-McLain representative for suggested piping and control methods.
prevent cold return water temperature
Failure to
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
the water temperature being supplied to the radiant
tubing.
8
Gauge
water temperature is accurately set for a minimum of
130°F. If this gauge is not available however, adjust the
valves such that the boiler-mounted temperature/pres-
sure gauge reads at least 150°F when the system return
water is cold (approximately 60°F water temperature).
Valve adjustment
(Figures 20 and 21 only)
radiant heating
1. Set the valves while the system is cool, setting for the
. For alterna-
coldest expected water temperature (usually 60°F
since the system will often drop to room tempera-
ture between cycles).
. Start with valve
3. Gradually open valve
the temperature at gauge
4a
reads 60°F.
4. Note that valve
ter from the boiler supply which mixes with return
water. Valve
flowing through the boiler secondary loop.
system supply temperature
and the
).
system supply temperature
provide controls and piping
no less than 130°F
at
required
is
on all systems to assure the return
7a
fully closed and
7a
while closing valve
8
reads 130°F when gauge
7a
regulates the amount of hot wa-
7b
regulates the amount of system water
to the boiler could cause corrosion of
regulating the boiler return
(such as provided by an
relatively constant.
is
which can
regulate the boiler re-
regardless of system supply temperature.
to the boiler could cause corrosion
Part Number 550-110-710/0107
7b
fully open.
7b
until
injec-
outdoor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents