Toshiba G8000 Series Installation Manual page 32

Uninterruptible power system (ups)
Hide thumbs Also See for G8000 Series:
Table of Contents

Advertisement

Three cable knockout plates are provided at bottom of each 100/125/150/180/225kVA UPS. Holes
are recommended in Figure 11.3.
The installing electrical contractor must punch the 5 holes.
4" Dia
0.8"
AC Input
Three solid rectangles show the cable knockout plates' outline. The dashed
rectangle shows the UPS opening under the plates.
Figure 11.3 - Cable knockout plates at the bottom (100~225kVA).
The terminal busses are shown in Figure 11.4. The busses are located inside of the 250/300kVA UPS at the
top. The dashed line shows the side view of the screw holes. The screws are used to tighten the lugs.
External cable size recommendations are located in Table 11.6 and 11.7. These tables show only the
torque to tighten a terminal bus & a corresponding lug. Torque to tighten the cable end in a
compression lug shall be specified by the lug vendor recommended in Table 11.8.
1
2
3
U
V
W
AC INPUT
BATTERY
3-phase 3-wire
Figure 11.4 - Terminal Busses of the 250/300kVA UPS.
Plate #1
.
0.4"
Bypass
4
5
6
7
U
V
-
+
BYPASS INPUT
3-phase 4-wire
31
Plate #2
Battery
AC Output
8
9
W
N
AC OUTPUT
3-phase 4-wire
Plate #3
2" Dia.
Control
Wires
10
11
12
U
V